2.3.5.8 

LD0.DPHHPDOC2 Three-phase directional overcurrent protection -

high stage (2)

Table 34:

LD0.DPHHPDOC2 Three-phase directional overcurrent protection - high stage (2)

IEC 61850 name

SA name

Description

Values

LD0.DPHHPTOC2

 

High stage (2)

 

.Op.general

OPERATE

-Operate

1=Operate

.Str.general

START

-Start

1=Start

2.3.5.9 

LD0.PHLPTOC1 Phase overcurrent protection - low stage 1

Table 35:

LD0.PHLPTOC1 Phase overcurrent protection - low stage 1

IEC 61850 name

SA name

Description

Values

LD0.PHLPTOC1

 

 

 

.Op.general

OPERATE

Stage operate

1=Operate

.Str.general

START

Stage start

1=Start

2.3.5.10 

LD0.PHIPTOC1 Phase overcurrent protection - instantaneous stage 1

Table 36:

LD0.PHIPTOC1 Phase overcurrent protection - instantaneous stage 1

IEC 61850 name

SA name

Description

Values

LD0.PHIPTOC1

 

 

 

.Op.general

OPERATE

Stage operate

1=Operate

.Str.general

START

Stage start

1=Start

2.3.5.11 

LD0.EFLPTOC1 Non-directional earth-fault and sensitive earth-fault

protection - low stage 1

Table 37:

LD0.EFLPTOC1 Non-directional earth-fault and sensitive earth-fault protection - low stage 1

IEC 61850 name

SA name

Description

Values

LD0.EFLPTOC1

 

Low stage (1)

 

.Op.general

OPERATE

-Operate

1=Operate

.Str.general

START

-Start

1=Start

1MRS757656 A

Section 2

DNP3 data mappings

REM620

27

Point List Manual

Summary of Contents for REM620

Page 1: ...Relion 620 series Motor Protection and Control REM620 DNP3 Point List Manual ...

Page 2: ......

Page 3: ...Document ID 1MRS757656 Issued 2013 05 07 Revision A Product version 2 0 Copyright 2013 ABB All rights reserved ...

Page 4: ...is document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of the ABB Group All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders Warranty Please inquire about the terms of warranty from your nearest ABB...

Page 5: ...product failure would create a risk for harm to property or persons including but not limited to personal injuries or death shall be the sole responsibility of the person or entity applying the equipment and those so responsible are hereby requested to ensure that all measures are taken to exclude or mitigate such risks This document has been carefully checked by ABB but deviations cannot be compl...

Page 6: ...erning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255 26 for the EMC directive and with the product standards EN 60255 1 and EN 60255 27 for the low voltage directive The product is designed in accordance with the international standa...

Page 7: ...RL Cxxxxx2 Circuit breaker 2 CB object and failure protection 19 CTRL Dxxxxx1 Controllable disconnector 1 20 CTRL Dxxxxx2 Controllable disconnector 2 20 CTRL Dxxxxx3 Controllable disconnector 3 20 CTRL Dxxxxx4 Controllable disconnector 4 21 CTRL Exxxxx1 Controllable earth switch 1 21 CTRL Exxxxx2 Controllable earth switch 2 21 LD0 EMSGAPC1 Emergency start 22 Sensors and monitoring functions 22 LD0...

Page 8: ...LD0 PHLPTOC1 Phase overcurrent protection low stage 1 27 LD0 PHIPTOC1 Phase overcurrent protection instantaneous stage 1 27 LD0 EFLPTOC1 Non directional earth fault and sensitive earth fault protection low stage 1 27 LD0 EFHPTOC1 Non directional earth fault and sensitive earth fault protection high stage 1 28 LD0 EFIPTOC1 Non directional earth fault and sensitive earth fault protection instantaneo...

Page 9: ...hase reversal protection 34 LD0 STTPMSU1 Motor startup supervision 34 LD0 LOFLPTUC1 Loss of load protection 34 LD0 LOFLPTUC2 Loss of load protection 34 Protection related functions 35 DR RDRE1 Disturbance recorder 35 LD0 CCRDIF1 Current circuit failure protection 35 LD0 SEQRFUF1 Fuse failure protection 35 LD0 SECRSYN1 Synchrocheck 35 Generic functions 36 LD0 MDSOPT1 Generic operation time supervis...

Page 10: ...s 1 42 LD0 FKEYGGIO1 LED states 42 Physical and raw I O data 43 LD0 XGGIO105 Physical I O 43 LD0 XHBGGIO105 Physical I O 43 LD0 XRGGIO105 Alarm warning 44 LD0 XRGGIO110 Alarm warning 44 LD0 XAGGIO130 Physical I O 44 LD0 XGGIO100 Physical I O 45 LD0 XBGGIO115 Physical I O 45 Binary outputs 46 System functions 46 LD0 DNPGGIO1 Parameter setting group control 46 LD0 LLN0 LPHD1 Reset indications and LE...

Page 11: ...ues 54 LD0 DNPGGIO1 Active parameter setting group 54 LD0 LEDGGIO1 LHMI LED indications 3 states 54 Switchgear functions 55 CTRL CBCSWI2 CB 4 pole 2 bit position value 55 CTRL CBCSWI1 CB 4 pole 2 bit position value 55 CTRL DCSXSWI1 Disconnector 1 4 pole 2 bit position values 55 CTRL DCSXSWI2 Disconnector 2 4 pole 2 bit position values 55 CTRL DCSXSWI3 Disconnector 3 4 pole 2 bit position values 55...

Page 12: ... LD0 VMMXU1 Voltage measurement 59 LD0 RESVMMXU1 Residual voltage 1 60 LD0 VSMSQI1 Sequence of voltage measurement 60 LD0 PEMMTR1 Power measurement and accumulated power values 60 LD0 FMMXU1 Frequency measurement 61 Protection functions 61 LD0 MPTTR1 Thermal protection 61 Protection related functions 61 DR RDRE1 Disturbance recorder values 61 LD0 SECRSYN1 Synchrocheck line and bus state 61 Physica...

Page 13: ... be used to find out when and for what purpose a typical protection function can be used The manual can also be used when calculating settings The communication protocol manual describes a communication protocol supported by the IED The manual concentrates on vendor specific implementations The engineering guide provides information for IEC 61850 engineering of the protection IEDs with PCM600 and ...

Page 14: ...ints specific to the IED The manual should be used in conjunction with the corresponding communication protocol manual The technical manual contains application and functionality descriptions and lists function blocks logic diagrams input and output signals setting parameters and technical data sorted per function The manual can be used as a technical reference during the engineering phase install...

Page 15: ... manual are spelled out in the glossary The glossary also contains definitions of important terms Push button navigation in the LHMI menu structure is presented by using the push button icons To navigate between the options use and HMI menu paths are presented in bold Select Main menu Settings WHMI menu names are presented in bold Click Information in the WHMI menu structure LHMI messages are show...

Page 16: ...taneous stage instance 1 EFIPTOC1 Io 1 50N 51N 1 Directional earth fault protection low stage instance 1 DEFLPDEF1 Io 1 67N 1 1 Directional earth fault protection high stage DEFHPDEF1 Io 1 67N 2 1 Residual overvoltage protection instance 1 ROVPTOV1 Uo 1 59G 1 Residual overvoltage protection instance 2 ROVPTOV2 Uo 2 59G 2 Residual overvoltage protection instance 3 ROVPTOV3 Uo 3 59G 3 Three phase un...

Page 17: ...TTPMSU1 Is2t n 1 49 66 48 51LR 1 Phase reversal protection PREVPTOC1 I2 1 46R 1 Thermal overload protection for motors MPTTR1 3Ith M 1 49M 1 Motor differential protection MPDIF1 3dl M 1 87M 1 Circuit breaker failure protection instance 1 CCBRBRF1 3I Io BF 1 51BF 51NBF 1 Circuit breaker failure protection instance 2 CCBRBRF2 3I Io BF 2 51BF 51NBF 2 Master trip instance 1 TRPPTRC1 Master Trip 1 94 8...

Page 18: ...ng switch control instance 2 ESXSWI2 I O ESC 2 I O ESC 2 Disconnector position indication instance 1 DCSXSWI1 I O DC 1 I O DC 1 Disconnector position indication instance 2 DCSXSWI2 I O DC 2 I O DC 2 Earthing switch position indication instance 1 ESSXSWI1 I O ES 1 I O ES 1 Disconnector position indication instance 3 DCSXSWI3 I O DC 3 I O DC 3 Disconnector position indication instance 4 DCSXSWI4 I O...

Page 19: ...nstance 2 TPGAPC2 TP 2 TP 2 Minimum pulse timer 2 pcs instance 3 TPGAPC3 TP 3 TP 3 Minimum pulse timer 2 pcs instance 4 TPGAPC4 TP 4 TP 4 Minimum pulse timer 2 pcs second resolution instance 1 TPSGAPC1 TPS 1 TPS 1 Minimum pulse timer 2 pcs second resolution instance 2 TPSGAPC2 TPS 2 TPS 2 Minimum pulse timer 2 pcs minute resolution instance 1 TPMGAPC1 TPM 1 TPM 1 Minimum pulse timer 2 pcs minute r...

Page 20: ...T1 UDCNT 1 UDCNT 1 Generic Up Down Counters instance 2 UDFCNT2 UDCNT 2 UDCNT 2 Generic Up Down Counters instance 3 UDFCNT3 UDCNT 3 UDCNT 3 Generic Up Down Counters instance 4 UDFCNT4 UDCNT 4 UDCNT 4 Generic Up Down Counters instance 5 UDFCNT5 UDCNT 5 UDCNT 5 Generic Up Down Counters instance 6 UDFCNT6 UDCNT 6 UDCNT 6 Generic Up Down Counters instance 7 UDFCNT7 UDCNT 7 UDCNT 7 Generic Up Down Count...

Page 21: ...ss assignments are Class 0 and Class 1 for binary inputs and Class 0 and Class 2 for analog inputs These assignments can be modified later Analog values are provided with default scalings The scalings can be freely modified by the user This list represents the superset of DNP3 points The actual set of available points meaning the actual set of available applications is determined by the IED s orde...

Page 22: ...RQ4 FRPFRQ5 FRPFRQ6 MNSPTOC1 MNSPTOC2 LOFLPTUC1 LOFLPTUC2 JAMPTOC1 STTPMSU1 PREVPTOC1 MPTTR1 MPDIF1 CCBRBRF1 CCBRBRF2 TRPPTRC1 TRPPTRC2 ARCSARC1 o ARCSARC2 o ARCSARC3 o MAPGAPC1 MAPGAPC2 MAPGAPC3 MAPGAPC4 MAPGAPC5 MAPGAPC6 MAPGAPC7 Table continues on next page Section 2 1MRS757656 A DNP3 data mappings 16 REM620 Point List Manual ...

Page 23: ...SWI4 ESXSWI2 DCSXSWI1 DCSXSWI2 ESSXSWI1 DCSXSWI3 DCSXSWI4 ESSXSWI2 ESMGAPC1 SECRSYN1 SSCBR1 SSCBR2 TCSSCBR1 TCSSCBR2 CCRDIF1 SEQRFUF1 MDSOPT1 MDSOPT2 CMMXU1 CMMXU2 CSMSQI1 RESCMMXU1 VMMXU1 RESVMMXU1 VSMSQI1 PEMMXU1 LDPMSTA1 Table continues on next page 1MRS757656 A Section 2 DNP3 data mappings REM620 17 Point List Manual ...

Page 24: ...ple in the Application Configuration tool in PCM600 Description Short description of the signal See the technical manual for more information Value Meaning of the input states 2 3 1 System functions 2 3 1 1 CTRL LLN0 Local remote state also present in DNP IIN bits Table 4 CTRL LLN0 Local remote state also present in DNP IIN bits IEC 61850 name SA name Description Values CTRL LLN0 Loc stVal Remote ...

Page 25: ...T Operate re trip 1 Operate Str general CB_FAULT_AL Start timer running 1 Start 2 3 2 2 CTRL Cxxxxx2 Circuit breaker 2 CB object and failure protection Table 7 CTRL Cxxxxx2 Circuit breaker 2 CB object and failure protection IEC 61850 name SA name Description Values CTRL CBCILO2 EnaCls stVal ENA_CLOSE Close enabled 1 Enabled EnaOpn stVal ENA_OPEN Open enabled 1 Enabled ItlByPss stVal ITL_BYPASS Int...

Page 26: ...ENA_CLOSE Close enabled 1 Enabled EnaOpn stVal ENA_OPEN Open enabled 1 Enabled ItlByPss stVal ITL_BYPASS Interlocking bypass 1 Bypassed CTRL DCCSWI2 Pos stSeld SELECTED CB selected 1 Selected CTRL DCXSWI2 BlkCls stVal BLK_CLOSE Close blocked 1 Blocked BlkOpn stVal BLK_OPEN Open blocked 1 Blocked 2 3 2 5 CTRL Dxxxxx3 Controllable disconnector 3 Table 10 CTRL Dxxxxx3 Controllable disconnector 3 IEC ...

Page 27: ... ENA_CLOSE Close enabled 1 Enabled EnaOpn stVal ENA_OPEN Open enabled 1 Enabled ItlByPss stVal ITL_BYPASS Interlocking bypass 1 Bypassed CTRL ESCSWI1 Pos stSeld SELECTED CB selected 1 Selected CTRL ESXSWI1 BlkCls stVal BLK_CLOSE Close blocked 1 Blocked BlkOpn stVal BLK_OPEN Open blocked 1 Blocked 2 3 2 8 CTRL Exxxxx2 Controllable earth switch 2 Table 13 CTRL Exxxxx2 Controllable earth switch 2 IEC...

Page 28: ...ARCPTRC11 Op general OPERATE Operate 1 Operate 2 3 3 2 LD0 ARCSARC2 Fault arc protection stage 2 Table 16 LD0 ARCSARC2 Fault arc protection stage 2 IEC 61850 name SA name Description Values LD0 ARCSARC21 FADet stVal ARC_FLT_DET Arc detected 1 Detected LD0 ARCPTRC21 Op general OPERATE Operate 1 Operate 2 3 3 3 LD0 ARCSARC3 Fault arc protection stage 3 Table 17 LD0 ARCSARC3 Fault arc protection stag...

Page 29: ...er condition monitoring Table 19 LD0 SSCBR2 Circuit breaker condition monitoring IEC 61850 name SA name Description Values APwrAlm stVal IPOW_ALM Iyt alarm 1 Alarm APwrLO stVal IPOW_LO Iyt lockout 1 Lockout CBLifAlm stVal CB_LIFE_ALM CB lifetime alarm 1 Alarm ClsAlm stVal TRV_T_CL_ALM Cls travel time alarm 1 Alarm LonTmAlm stVal MON_ALM CB inactive alarm 1 Alarm OpnAlm stVal TRV_T_OP_ALM Cls trave...

Page 30: ...arm 1 Alarm LoWrn stVal LOW_WARN Low warning 1 Warning 2 3 4 2 LD0 CMMXU2 Phase currents 2 limit supervision Table 23 LD0 CMMXU2 Phase currents 2 limit supervision IEC 61850 name SA name Description Values LD0 CMMXU2 HiAlm stVal HIGH_ALARM High alarm 1 Alarm HiWrn stVal HIGH_WARN High warning 1 Warning LoAlm stVal LOW_ALARM Low alarm 1 Alarm LoWrn stVal LOW_WARN Low warning 1 Warning 2 3 4 3 LD0 R...

Page 31: ...WARN High warning 1 Warning 2 3 5 Protection functions 2 3 5 1 LD0 LEDPTRC1 Global protection signals Table 27 LD0 LEDPTRC1 Global protection signals IEC 61850 name SA name Description Values LD0 LEDPTRC1 Global protection signals Op general General Operate 1 Operate Op phsA phsA Operate 1 Operate Op phsB phsB Operate 1 Operate Op phsC phsC Operate 1 Operate Str general General Start 1 Start Str p...

Page 32: ...stage 1 IEC 61850 name SA name Description Values LD0 DEFHPTOC1 High stage 1 Op general OPERATE Operate 1 Operate Str general START Start 1 Start 2 3 5 6 LD0 DPHLPDOC1 Three phase directional overcurrent protection low stage 1 Table 32 LD0 DPHLPDOC1 Three phase directional overcurrent protection low stage 1 IEC 61850 name SA name Description Values LD0 DPHLPTOC1 Low stage 1 Op general OPERATE Oper...

Page 33: ...e Str general START Stage start 1 Start 2 3 5 10 LD0 PHIPTOC1 Phase overcurrent protection instantaneous stage 1 Table 36 LD0 PHIPTOC1 Phase overcurrent protection instantaneous stage 1 IEC 61850 name SA name Description Values LD0 PHIPTOC1 Op general OPERATE Stage operate 1 Operate Str general START Stage start 1 Start 2 3 5 11 LD0 EFLPTOC1 Non directional earth fault and sensitive earth fault pr...

Page 34: ...rate Str general START Start 1 Start 2 3 5 14 LD0 PHPTOV1 Phase overvoltage protection stage 1 Table 40 LD0 PHPTOV1 Phase overvoltage protection stage 1 IEC 61850 name SA name Description Values LD0 PHPTOV1 Op general OPERATE Stage operate 1 Operate Str general START Stage start 1 Start 2 3 5 15 LD0 PHPTOV2 Phase overvoltage protection stage 2 Table 41 LD0 PHPTOV2 Phase overvoltage protection stag...

Page 35: ...Table 45 LD0 PHPTUV3 Phase undervoltage protection stage 3 IEC 61850 name SA name Description Values LD0 PHPTUV3 Op general OPERATE Stage operate 1 Operate Str general START Stage start 1 Start 2 3 5 20 LD0 ROVPTOV1 Residual overvoltage protection 1 Table 46 LD0 ROVPTOV1 Residual overvoltage protection 1 IEC 61850 name SA name Description Values LD0 ROVPTOV1 Op general OPERATE Stage 1 operate 1 Op...

Page 36: ...0 LD0 MNSPTOC2 Negative sequence overcurrent protection for motors 2 IEC 61850 name SA name Description Values LD0 MNSPTOC2 Op general OPERATE Stage operate 1 Operate Str general START Stage start 1 Start 2 3 5 25 LD0 NSPTOV1 Negative sequence overvoltage protection stage 1 Table 51 LD0 NSPTOV1 Negative sequence overvoltage protection stage 1 IEC 61850 name SA name Description Values LD0 NSPTOV1 O...

Page 37: ...tection 1 Table 55 LD0 FRPFRQ1 Frequency protection 1 IEC 61850 name SA name Description Values LD0 FRPTRC1 Str general START Stage start 1 Start LD0 FRPTOF1 Overfrequency Op general OPR_OFRQ Operate 1 Operate LD0 FRPTUF1 Underfrequency Op general OPR_UFRQ Operate 1 Operate LD0 FRPFRC1 Frequency gradient Op general OPR_FRG Operate 1 Operate 2 3 5 30 LD0 FRPFRQ2 Frequency protection 2 Table 56 LD0 ...

Page 38: ... Values LD0 FRPTRC4 Str general START Stage start 1 Start LD0 FRPTOF4 Overfrequency Op general OPR_OFRQ Operate 1 Operate LD0 FRPTUF4 Underfrequency Op general OPR_UFRQ Operate 1 Operate LD0 FRPFRC4 Frequency gradient Op general OPR_FRG Operate 1 Operate 2 3 5 33 LD0 FRPFRQ5 Frequency protection 5 Table 59 LD0 FRPFRQ5 Frequency protection 5 IEC 61850 name SA name Description Values LD0 FRPTRC5 Str...

Page 39: ...on IEC 61850 name SA name Description Values LD0 JAMPTOC1 Op general OPERATE Stage operate 1 Operate 2 3 5 36 LD0 MPDIF1 Motor differential protection 1 Table 62 LD0 MPDIF1 Motor differential protection 1 IEC 61850 name SA name Description Values LD0 MPDIF1 Op general OPERATE Stage operate 1 Operate 2 3 5 37 LD0 MPTTR1 Motor thermal overload protection Table 63 LD0 MPTTR1 Motor thermal overload pr...

Page 40: ...0 STTPMSS1 Op general OPR_IIT Stalling operate 1 Operate Str general MOT_START Startup in progress 1 In progress 2 3 5 40 LD0 LOFLPTUC1 Loss of load protection Table 66 LD0 LOFLPTUC1 Loss of load protection IEC 61850 name SA name Description Values LD0 LOFLPTUC1 Op general OPERATE Stage operate 1 Operate Str general START Stage start 1 Start 2 3 5 41 LD0 LOFLPTUC2 Loss of load protection Table 67 ...

Page 41: ... Operate 1 Operate 2 3 6 3 LD0 SEQRFUF1 Fuse failure protection Table 70 LD0 SEQRFUF1 Fuse failure protection IEC 61850 name SA name Description Values LD0 SEQRFUF1 Str general FUSEF_U General start 1 Start Str3Ph general FUSEF_3PH Three phase start 1 Start 2 3 6 4 LD0 SECRSYN1 Synchrocheck Table 71 LD0 SECRSYN1 Synchrocheck IEC 61850 name SA name Description Values LD0 SECRSYN1 SynPrg stVal SYNC_...

Page 42: ...on function 1 Table 74 LD0 MAPGAPC1 Multipurpose analog protection function 1 IEC 61850 name SA name Description Values LD0 MAPGAPC1 Op general OPERATE Stage operate 1 Operate Str general START Stage start 1 Start 2 3 7 4 LD0 MAPGAPC2 Multipurpose analog protection function 2 Table 75 LD0 MAPGAPC2 Multipurpose analog protection function 2 IEC 61850 name SA name Description Values LD0 MAPGAPC2 Op g...

Page 43: ...le 79 LD0 MAPGAPC6 Multipurpose analog protection function 6 IEC 61850 name SA name Description Values LD0 MAPGAPC6 Op general OPERATE Stage operate 1 Operate Str general START Stage start 1 Start 2 3 7 9 LD0 MAPGAPC7 Multipurpose analog protection function 7 Table 80 LD0 MAPGAPC7 Multipurpose analog protection function 7 IEC 61850 name SA name Description Values LD0 MAPGAPC7 Op general OPERATE St...

Page 44: ...APGAPC11 Multipurpose analog protection function 11 IEC 61850 name SA name Description Values LD0 MAPGAPC11 Op general OPERATE Stage operate 1 Operate Str general START Stage start 1 Start 2 3 7 14 LD0 MAPGAPC12 Multipurpose analog protection function 12 Table 85 LD0 MAPGAPC12 Multipurpose analog protection function 12 IEC 61850 name SA name Description Values LD0 MAPGAPC12 Op general OPERATE Stag...

Page 45: ...Q4 stVal Input 4 signal 0 1 Off On Q5 stVal Input 5 signal 0 1 Off On Q6 stVal Input 6 signal 0 1 Off On Q7 stVal Input 7 signal 0 1 Off On Q8 stVal Input 8 signal 0 1 Off On 2 3 7 17 LD0 MVGAPC3 Multipurpose binary inputs 3 Table 88 LD0 MVGAPC3 Multipurpose binary inputs 3 IEC 61850 name SA name Description Values LD0 MVGAPC3 Q1 stVal Input 1 signal 0 1 Off On Q2 stVal Input 2 signal 0 1 Off On Q...

Page 46: ...EC 61850 name SA name Description Values LD0 SPCGGIO1 SPCS01 stVal Output 1 state 0 1 Off On SPCS02 stVal Output 2 state 0 1 Off On SPCS03 stVal Output 3 state 0 1 Off On SPCS04 stVal Output 4 state 0 1 Off On SPCS05 stVal Output 5 state 0 1 Off On SPCS06 stVal Output 6 state 0 1 Off On SPCS07 stVal Output 7 state 0 1 Off On SPCS08 stVal Output 8 state 0 1 Off On SPCS09 stVal Output 9 state 0 1 Of...

Page 47: ...tVal Output 14 state 0 1 Off On SPCS15 stVal Output 15 state 0 1 Off On SPCS16 stVal Output 16 state 0 1 Off On 2 3 7 21 LD0 SPCGGIO3 Multipurpose binary outputs status 3 Table 92 LD0 SPCGGIO3 Multipurpose binary outputs status 3 IEC 61850 name SA name Description Values LD0 SPCGGIO3 SPCS01 stVal Output 1 state 0 1 Off On SPCS02 stVal Output 2 state 0 1 Off On SPCS03 stVal Output 3 state 0 1 Off O...

Page 48: ...0 1 Off On SPCS09 stVal Output 9 state 0 1 Off On SPCS10 stVal Output 10 state 0 1 Off On SPCS11 stVal Output 11 state 0 1 Off On SPCS12 stVal Output 12 state 0 1 Off On SPCS13 stVal Output 13 state 0 1 Off On SPCS14 stVal Output 14 state 0 1 Off On SPCS15 stVal Output 15 state 0 1 Off On SPCS16 stVal Output 16 state 0 1 Off On 2 3 7 23 LD0 FKEYGGIO1 LED states Table 94 LD0 FKEYGGIO1 LED states IE...

Page 49: ...stVal X105 Input 3 1 0 ON OFF Ind4 stVal X105 Input 4 1 0 ON OFF Ind5 stVal X105 Input 5 1 0 ON OFF Ind6 stVal X105 Input 6 1 0 ON OFF Ind7 stVal X105 Input 7 1 0 ON OFF Ind8 stVal X105 Input 8 1 0 ON OFF SPCSO1 stVal X105 Output 1 1 0 ON OFF SPCSO2 stVal X105 Output 2 1 0 ON OFF SPCSO3 stVal X105 Output 3 1 0 ON OFF SPCSO4 stVal X105 Output 4 1 0 ON OFF 2 3 8 2 LD0 XHBGGIO105 Physical I O Table 9...

Page 50: ... stVal XRGGIO105 Alarm 1 Alarm Wrn stVal XRGGIO105 Warning 1 Warning 2 3 8 4 LD0 XRGGIO110 Alarm warning Table 98 LD0 XRGGIO110 Alarm warning IEC 61850 name SA name Description Values LD0 XRGGIO110 Alm stVal XRGGIO110 Alarm 1 Alarm Wrn stVal XRGGIO110 Warning 1 Warning 2 3 8 5 LD0 XAGGIO130 Physical I O Table 99 LD0 XAGGIO130 Physical I O IEC 61850 name SA name Description Values LD0 XAGGIO130 Ind...

Page 51: ...1 LD0 XBGGIO115 Physical I O IEC 61850 name SA name Description Values LD0 XBGGIO115 Ind1 stVal XB115 Input 1 1 0 ON OFF Ind2 stVal XB115 Input 2 1 0 ON OFF Ind3 stVal XB115 Input 3 1 0 ON OFF Ind4 stVal XB115 Input 4 1 0 ON OFF Ind5 stVal XB115 Input 5 1 0 ON OFF Ind6 stVal XB115 Input 6 1 0 ON OFF Ind7 stVal XB115 Input 7 1 0 ON OFF Ind8 stVal XB115 Input 8 1 0 ON OFF SPCSO1 stVal XB115 Output 1...

Page 52: ...ffect the function of the output See the DNP3 control relay output block parameters 2 4 1 System functions 2 4 1 1 LD0 DNPGGIO1 Parameter setting group control Table 103 LD0 DNPGGIO1 Parameter setting group control IEC 61850 name SA name Description Type LD0 DNPGGIO1 ActSG1 ctlVal Setting group 1 On ActSG2 ctlVal Setting group 2 On ActSG3 ctlVal Setting group 3 On ActSG4 ctlVal Setting group 4 On ...

Page 53: ... control Table 107 CTRL DCCSWI1 Controllable disconnector 1 control IEC 61850 name SA name Description Type CTRL DCCSWI1 Pos Oper ctlVal Disconnector control On Off 2 4 2 4 CTRL DCCSWI2 Controllable disconnector 2 control Table 108 CTRL DCCSWI2 Controllable disconnector 2 control IEC 61850 name SA name Description Type CTRL DCCSWI2 Pos Oper ctlVal Disconnector control On Off 2 4 2 5 CTRL DCCSWI3 C...

Page 54: ...trol Table 112 CTRL ESCSWI2 Controllable earth switch 2 control IEC 61850 name SA name Description Type CTRL ESCSWI2 Pos Oper ctlVal Earth switch control On Off 2 4 3 Sensors and monitoring functions 2 4 3 1 LD0 SSCBR1 Reset signals of CB condition monitoring Table 113 LD0 SSCBR1 Reset signals of CB condition monitoring IEC 61850 name SA name Description Type LD0 SSCBR1 RsAccAPwr Oper ctlVal RST_I...

Page 55: ... SA name Description Type LD0 PEMMXU1 SupDmdRs Oper ctlVal RSTACM Reset accum energy On 2 4 5 Protection related functions 2 4 5 1 DR RDRE1 Disturbance recorder Table 116 DR RDRE1 Disturbance recorder IEC 61850 name SA name Description Type DR RDRE1 MemClr Oper ctlVal Clear all records On RcdTrg Oper ctlVal Trig recording On 2 4 6 Generic functions 2 4 6 1 LD0 SPCGGIO1 Multipurpose binary outputs ...

Page 56: ... 6 2 LD0 SPCGGIO2 Multipurpose binary outputs 2 The binary outputs can be configured either as pulse or persistent type outputs Pulse type outputs are triggered with the write value 1 Persistent type outputs can be written with both values 1 and 0 The setting mode toggled for local operation corresponds to persistent for remote operation Table 118 LD0 SPCGGIO2 Multipurpose binary outputs 2 IEC 618...

Page 57: ...Output 2 control On Off SPCS03 ctlVal Output 3 control On Off SPCS04 ctlVal Output 4 control On Off SPCS05 ctlVal Output 5 control On Off SPCS06 ctlVal Output 6 control On Off SPCS07 ctlVal Output 7 control On Off SPCS08 ctlVal Output 8 control On Off SPCS09 ctlVal Output 9 control On Off SPCS10 ctlVal Output 10 control On Off SPCS11 ctlVal Output 11 control On Off SPCS12 ctlVal Output 12 control ...

Page 58: ...rol On Off SPCS12 ctlVal Output 12 control On Off SPCS13 ctlVal Output 13 control On Off SPCS14 ctlVal Output 14 control On Off SPCS15 ctlVal Output 15 control On Off SPCS16 ctlVal Output 16 control On Off 2 4 6 5 LD0 SRGAPC1 Multipurpose binary outputs flip flop resets 1 Table 121 LD0 SRGAPC1 Multipurpose binary outputs flip flop resets 1 IEC 61850 name SA name Description Type LD0 SRGAPC1 Rs1 ct...

Page 59: ...me The signal may have a defined label that is visible for example in the Application Configuration tool in PCM600 Description Short description of the signal See the technical manual for more information Values The value range of the original IEC 61850 data Scaling is needed to convert floating point data into DNP3 integer values S Scaling type selected as default Default R means ratio scaling Se...

Page 60: ...1 ActSG stVal Active setting group 1 6 R 1 6 1 6 2 5 1 4 LD0 LEDGGIO1 LHMI LED indications 3 states Table 127 LD0 LEDGGIO1 LHMI LED indications 3 states IEC 61850 name SA name Description Values S Arg 1 2 3 4 LD0 LEDGGIO1 ISCSO1 stVal LED 1 state 0 1 3 Off Ok Alarm R 0 3 0 3 ISCSO2 stVal LED 2 state 0 1 3 Off Ok Alarm R 0 3 0 3 ISCSO3 stVal LED 3 state 0 1 3 Off Ok Alarm R 0 3 0 3 ISCSO4 stVal LED...

Page 61: ...XSWI1 Disconnector 1 4 pole 2 bit position values IEC 61850 name SA name Description Values S Arg 1 2 3 4 CTRL DCSXSWI1 Pos stVal POSITION Intermediate 0 Off 1 On 2 Bad 3 0 3 R 0 3 0 3 2 5 2 4 CTRL DCSXSWI2 Disconnector 2 4 pole 2 bit position values Table 131 CTRL DCSXSWI2 Disconnector 2 4 pole 2 bit position values IEC 61850 name SA name Description Values S Arg 1 2 3 4 CTRL DCSXSWI2 Pos stVal P...

Page 62: ... DCXSWI2 Controllable disconnector 2 4 pole 2 bit position values IEC 61850 name SA name Description Values S Arg 1 2 3 4 CTRL DCXSWI2 Pos stVal POSITION Intermediate 0 Off 1 On 2 Bad 3 0 3 R 0 3 0 3 2 5 2 9 CTRL DCXSWI3 Controllable disconnector 3 4 pole 2 bit position values Table 136 CTRL DCXSWI3 Controllable disconnector 3 4 pole 2 bit position values IEC 61850 name SA name Description Values ...

Page 63: ...ermediate 0 Off 1 On 2 Bad 3 0 3 R 0 3 0 3 2 5 2 13 CTRL ESXSWI1 Controllable earth switch 1 4 pole 2 bit position values Table 140 CTRL ESXSWI1 Controllable earth switch 1 4 pole 2 bit position values IEC 61850 name SA name Description Values S Arg 1 2 3 4 CTRL ESXSWI1 Pos stVal POSITION Intermediate 0 Off 1 On 2 Bad 3 0 3 R 0 3 0 3 2 5 2 14 CTRL ESXSWI2 Controllable earth switch 2 4 pole 2 bit p...

Page 64: ...0 60000 R 0 60000 0 60000 TmsSprCha mag f Spring charge time 0 99 99 R 0 99 99 0 9999 2 5 3 2 LD0 SSCBR2 Circuit breaker condition monitoring values Table 143 LD0 SSCBR2 Circuit breaker condition monitoring values IEC 61850 name SA name Description Values S Arg 1 2 3 4 LD0 SSCBR2 AccAPwrPhA mag Iyt value phase A 0 1e6 R 0 1E6 0 1E6 AccAPwrPhB mag Iyt value phase B 0 1e6 R 0 1E6 0 1E6 AccAPwrPhC ma...

Page 65: ...uence of currents Table 146 LD0 CSMSQI1 Sequence of currents IEC 61850 name SA name Description Values S Arg 1 2 3 4 LD0 CSMSQI1 Sequence of currents SeqA c1 instCVal mag I1_INST Positive magnitude 0 00 40 0 xIn R 0 40 0 4000 SeqA c2 instCVal mag I2_INST Negative magnitude 0 00 40 0 xIn R 0 40 0 4000 SeqA c3 instCVal mag I3_INST Zero magnitude 0 00 40 0 xIn R 0 40 0 4000 2 5 4 4 LD0 VMMXU1 Voltage...

Page 66: ...SeqV c2 cVal mag I2_DB Negative magnitude 0 00 4 00 xUn R 0 4 0 400 SeqV c3 cVal mag I3_DB Zero magnitude 0 00 4 00 xUn R 0 4 0 400 2 5 4 7 LD0 PEMMTR1 Power measurement and accumulated power values Table 150 LD0 PEMMTR1 Power measurement and accumulated power values IEC 61850 name SA name Description Values S Arg 1 2 3 4 LD0 PEMMTR1 DmdVArh actVal ER_RV_ACM Forward reactive energy 0 1e10 R 0 1E10...

Page 67: ...99 R 99 999 99 999 2 5 6 Protection related functions 2 5 6 1 DR RDRE1 Disturbance recorder values Table 153 DR RDRE1 Disturbance recorder values IEC 61850 name SA name Description Values S Arg 1 2 3 4 DR RDRE1 FltNum stVal Number of recordings 0 65535 R 0 65535 0 65535 MemUsed stVal Rec memory used 0 100 R 0 100 0 100 2 5 6 2 LD0 SECRSYN1 Synchrocheck line and bus state Table 154 LD0 SECRSYN1 Syn...

Page 68: ...R 1E4 1E4 1E4 1E4 AnIn8 instMag AI_VAL8 RTD input 8 10000 10000 R 1E4 1E4 1E4 1E4 2 5 7 2 LD0 XRGGIO110 RTD inputs Table 156 LD0 XRGGIO110 RTD inputs IEC 61850 name SA name Description Values S Arg 1 2 3 4 LD0 XRGGIO110 AnIn1 instMag AI_VAL1 RTD input 1 10000 10000 R 1E4 1E4 1E4 1E4 AnIn2 instMag AI_VAL2 RTD input 2 10000 10000 R 1E4 1E4 1E4 1E4 AnIn3 instMag AI_VAL3 RTD input 3 10000 10000 R 1E4 ...

Page 69: ...ls supported the complete list is described in the attached table For static non change event object requests request qualifier codes 07 and 08 limited quantity and 17 and 28 index are supported Static object requests sent with qualifiers 07 or 08 will be responded with qualifiers 00 or 01 16 bit and 32 bit Analog Change Events with Time may be requested Maximum data link frame size octets Maximum...

Page 70: ...Count 1 Count 1 is accepted but ignored Never Always Sometimes Configurable Pulse on Never Always Sometimes Configurable Pulse off Never Always Sometimes Configurable Latch on Never Always Sometimes Configurable Latch off Never Always Sometimes Configurable Queue Never Always Sometimes Configurable Clear queue Never Always Sometimes Configurable The circuit breaker control model is configurable fo...

Page 71: ...ort Append file mode Yes No Custom status code strings Yes No Permissions field Yes No File events assigned to class Yes No File events send immediately Yes No Multiple blocks in a fragment Yes No Max number of files open 0 Selected Not selected 3 2 DNP3 implementation table The following table identifies which object variations function codes and qualifiers the IED supports in both request messag...

Page 72: ...0 unsol resp 17 28 index 2 21 Binary input change with time 1 read 06 no range or all 07 08 limited qty 129 response 130 unsol resp 17 28 index 2 3 Binary input change with relative time 1 read 06 no range or all 07 08 limited qty 129 response 130 unsol resp 17 28 index 10 0 Binary output status any variation 1 read 00 01 start stop 06 no range or all 07 08 limited qty 17 28 index 10 1 Binary outp...

Page 73: ...sp 17 28 index 32 2 16 bit analog change event without time 1 read 06 no range or all 07 08 limited qty 129 response 130 unsol resp 17 28 index 32 3 32 bit analog change event with time 1 read 06 no range or all 07 08 limited qty 129 response 130 unsol resp 17 28 index 32 4 default 1 16 bit analog change event with time 1 read 06 no range or all 07 08 limited qty 129 response 130 unsol resp 17 28 ...

Page 74: ...restart 4 No object function code only 23 delay meas No object function code only 24 record current time 1 A default variation refers to the variation responded when variation 0 is requested and or in class 0 1 2 or 3 scans Default variations are configurable however default settings for the configuration parameters are indicated in the table above 2 For static non change event objects qualifiers ...

Page 75: ...p of the protocol and assumes responsibility for its evolution EMC Electromagnetic compatibility HMI Human machine interface IEC International Electrotechnical Commission IEC 61850 International standard for substation communication and modeling IED Intelligent electronic device IET600 Integrated Engineering Toolbox in PCM600 LHMI Local human machine interface PCM600 Protection and Control IED Man...

Page 76: ...70 ...

Page 77: ...71 ...