2.4.2.6
CTRL.DCCSWI4 Controllable disconnector (4) control
Table 110:
CTRL.DCCSWI4 Controllable disconnector (4) control
IEC 61850 name
SA name
Description
Type
CTRL.DCCSWI4
.Pos.Oper.ctlVal
-
Disconnector control
On/Off
2.4.2.7
CTRL.ESCSWI1 Controllable earth switch (1) control
Table 111:
CTRL.ESCSWI1 Controllable earth switch (1) control
IEC 61850 name
SA name
Description
Type
CTRL.ESCSWI1
.Pos.Oper.ctlVal
-
Earth switch control
On/Off
2.4.2.8
CTRL.ESCSWI2 Controllable earth switch (2) control
Table 112:
CTRL.ESCSWI2 Controllable earth switch (2) control
IEC 61850 name
SA name
Description
Type
CTRL.ESCSWI2
.Pos.Oper.ctlVal
-
Earth switch control
On/Off
2.4.3
Sensors and monitoring functions
2.4.3.1
LD0.SSCBR1 Reset signals of CB condition monitoring
Table 113:
LD0.SSCBR1 Reset signals of CB condition monitoring
IEC 61850 name
SA name
Description
Type
LD0.SSCBR1
.RsAccAPwr.Oper.ctlVal
RST_IPOW
Reset accum. energy
On
.RsCBWear.Oper.ctlVal
RST_CB_WEAR
Reset CB life and op. counter
On
.RsSprChaTm.Oper.ctlVal
RST_SPR_T
Reset spring charge alarm
On
.RsTrvTm.Oper.ctlVal
RST_TRV_T
Reset travel time alarm
On
Section 2
1MRS757656 A
DNP3 data mappings
48
REM620