2.3.2.3
CTRL.Dxxxxx1 Controllable disconnector (1)
Table 8:
CTRL.Dxxxxx1 Controllable disconnector (1)
IEC 61850 name
SA name
Description
Values
CTRL.DCCILO1
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
.ItlByPss.stVal
ITL_BYPASS
Interlocking bypass
1=Bypassed
CTRL.DCCSWI1
.Pos.stSeld
SELECTED
CB selected
1=Selected
CTRL.DCXSWI1
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
2.3.2.4
CTRL.Dxxxxx2 Controllable disconnector (2)
Table 9:
CTRL.Dxxxxx2 Controllable disconnector (2)
IEC 61850 name
SA name
Description
Values
CTRL.DCCILO2
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
.ItlByPss.stVal
ITL_BYPASS
Interlocking bypass
1=Bypassed
CTRL.DCCSWI2
.Pos.stSeld
SELECTED
CB selected
1=Selected
CTRL.DCXSWI2
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
2.3.2.5
CTRL.Dxxxxx3 Controllable disconnector (3)
Table 10:
CTRL.Dxxxxx3 Controllable disconnector (3)
IEC 61850 name
SA name
Description
Values
CTRL.DCCILO3
.EnaCls.stVal
ENA_CLOSE
Close enabled
1=Enabled
.EnaOpn.stVal
ENA_OPEN
Open enabled
1=Enabled
.ItlByPss.stVal
ITL_BYPASS
Interlocking bypass
1=Bypassed
CTRL.DCCSWI3
.Pos.stSeld
SELECTED
CB selected
1=Selected
CTRL.DCXSWI3
.BlkCls.stVal
BLK_CLOSE
Close blocked
1=Blocked
.BlkOpn.stVal
BLK_OPEN
Open blocked
1=Blocked
Section 2
1MRS757656 A
DNP3 data mappings
20
REM620
Point List Manual