Table 26. Phase reversal protection (REV)
Feature
Value
Trip value
NPS ≥75% of the maximum phase current
Time/current characteristic
• Definite time operate time
220 ms ±50 ms
Resetting time, typical
100...200 ms
Drop-off/pick-up ratio, typical
0.95
Table 27. Cumulative startup time counter and restart inhibit function (
Σ
tsi
)
Feature
Value
Set restart inhibit value,
Σ
tsi
5...500 s
Countdown rate of startup time counter,
Δ
Σ
ts
/
Δ
t
2...250 s/h
Table 28. Temperature protection using RTD sensors or thermistors (ThA> and ThB>)
Feature
Value
Operate time accuracy at definite-time
characteristic
±3% of the set operate time or 200 ms
1)
RTD sensors
Set alarm value, Ta1...6>
0...200ºC
Operate time, ta1...6>
1...100 s
Set trip value, Tp1...6>
0...200ºC
Operate time, tp1...6>
1...100 s
Hysteresis
5ºC
Operation accuracy
±1 ºC (±3ºC for Cu10)
Thermistors
Set trip value, Thp1> and Thp2>
0.1...15.0 kΩ
Operate time
2 s
Operation accuracy
±1% of the setting range
1) Note the response time of the RTD card (<8 s).
Motor Protection
1MRS756304 C
REM610
Product version: C
Issued: 30.10.2009
ABB
23