Table 22. Three-phase instantaneous or definite time short circuit protection (I>>)
Feature
Value
Set start value, I>>
• At definite-time characteristic
0.50...20.0 x I
n
Start time, typical
50 ms
Time/current characteristic
• Definite time operate time, t>
0.05...30.0 s
Resetting time, typical/maximum
40/50 ms
Retardation time
30 ms
Drop-off/pick-up ratio, typical
0.96
Operate time accuracy at definite-time
characteristic
±2% of the set operate time or ±25 ms
Operation accuracy
±3% of the set start value
Table 23. Definite-time undercurrent (loss-of-load) protection (I<)
Feature
Value
Set start value, I<
• At definite-time characteristic
30...80% I
n
Start time, typical
300 ms
Time/current characteristic
• Definite time operate time, t<
2...600 s
Resetting time, typical/maximum
300/350 ms
Drop-off/pick-up ratio, typical
1.1
Inhibitation of I<
<12% I
n
Operate time accuracy at
• Definite-time characteristic
±3% of the set operate time or 100 ms
Operation accuracy
±3% of the set start value or +0.5% I
n
Motor Protection
1MRS756304 C
REM610
Product version: C
Issued: 30.10.2009
ABB
21