Table 5. Energizing inputs
Description
Value
Rated frequency
50/60 Hz ±5 Hz
Rated current, I
n
1 A
5 A
Thermal withstand capability:
• Continuously
4 A
20 A
• For 1 s
100 A
500 A
• For 10 s
25 A
100 A
Dynamic current withstand:
• Half-wave value
250 A
1250 A
Input impedance
<100 mΩ
<20 mΩ
Table 6. Measuring range
Description
Value
Measured currents on phases I
L1
, I
L2
and I
L3
as multiples of the rated currents of the
energizing inputs
0... 50 × I
n
Earth-fault current as a multiple of the rated
current of the energizing input
0... 8 × I
n
Table 7. Digital inputs
Description
Value
Rated voltage
DI1, DI2
DI3...DI5 (optional)
• REM610BxxHxxx
Activating threshold
• REM610BxxLxxx
Activating threshold
110/125/220/250 V DC
Max. 88 V DC (110 V DC -20%)
24/48/60/110/125/220/250 V DC
Max. 19.2 V DC (24 V DC -20%)
• REM610BxxxxMx
Activating threshold
24/48/60/110/125/220/250 V DC
Max. 19.2 V DC (24 V DC -20%)
Operating range
±20% of the rated voltage
Current drain
2...18 mA
Power consumption/
input
<0.9 W
Motor Protection
1MRS756304 C
REM610
Product version: C
Issued: 30.10.2009
12
ABB