12. Technical data
Table 3. Dimensions
Description
Value
Width
frame
case
177 mm
164 mm
Height
frame
case
177 mm (4U)
160 mm
Depth
case
149.3 mm
Weight
IED
spare unit
3.5 kg
1.8 kg
Table 4. Power supply
Description
Value
Type
REM610CxxHxxx
REM610xxLxxx
U
aux
rated
U
r
= 100/110/120/220/240 V
AC
U
r
= 110/125/220/250 V DC
U
r
= 24/48/60 V DC
U
aux
variation (temporary)
85...110% of U
r
(AC)
80...120% of U
r
(DC)
80...120% of U
r
(DC)
Burden of auxiliary voltage
supply under quiescent (P
q
)/
operating condition
<9 W/13 W
Ripple in the DC auxiliary
voltage
Max. 12% of the DC value (at frequency ogf 100 Hz)
Interruption time in the
auxiliary DC voltage without
resetting the IED
<50 ms at U
aux
rated
Time to trip from switching
on the auxiliary voltage
1)
<350 ms
Internal over temperature
limit
+100 ºC
Fuse type
T2A/250 V
1) Time to trip of stages I>>
Motor Protection
1MRS756304 C
REM610
Product version: C
Issued: 30.10.2009
ABB
11
Summary of Contents for REM 610
Page 1: ...Relion 610 series Motor Protection REM610 Product Guide...
Page 34: ...34...