Table 16. Electromagnetic compatibility tests
Description
Type test value
Reference
EMC immunity test level meets the requirements listed below
1 MHz burst disturbance test,
class III
IEC 60255-22-1, IEC
61000-4-18
• Common mode
2.5 kV
• Differential mode
1.0 kV
Electrostatic discharge test,
class IV
IEC 61000-4-2, IEC
60255-22-2 and ANSI
C37.90.3-2001
• For contact discharge
8 kV
• For air discharge
15 kV
Radio frequency interference
tests
• Conducted, common mode
10 V (rms), f = 150 kHz...80
MHz
IEC 61000-4-6 and IEC
60255-22-6
• Radiated, amplitude-
modulated
10 V/m (rms), f = 80...2700
MHz
IEC 61000-4-3 and IEC
60255-22-3
• Radiated, pulse-modulated
10 V/m, f = 900 MHz
ENV 50204 and IEC
60255-22-3
Fast transient disturbance
tests
IEC 60255-22-4 and IEC
61000-4-4
• Power outputs, energizing
inputs, power supply
4 kV
• I/O ports
2 kV
Surge immunity test
IEC 61000-4-5 and IEC
60255-22-5
• Power outputs, energizing
inputs, power supply
4 kV, line-to-earth
2 kV, line-to-line
• I/O ports
2 kV, line-to earth
1 kV, line-to-line
Power frequency (50 Hz)
magnetic field
300 A/m continuous
IEC 6100-4-8
Power frequency immunity
test:
IEC 60255-22-7 and IEC
61000-4-16
Motor Protection
1MRS756304 C
REM610
Product version: C
Issued: 30.10.2009
ABB
17
Summary of Contents for REM 610
Page 1: ...Relion 610 series Motor Protection REM610 Product Guide...
Page 34: ...34...