1.
In the
Plant Structure
view, right-click the bay, point to
New
, point to the relay
application area such as
Multiapplication IEDs
and select the protection relay
type to be inserted.
Alternatively, drag an IED from the
Object Types
view to the
bay level.
2.
On the
Configuration mode selection
page, select
Offline configuration
and
click
Next
.
Setting up an IED in the offline mode is similar to the online mode; however,
with the offline mode it is not necessary to type the correct IP address in the
IP
address
box.
GUID-B4B6B577-1C7B-40C2-BD9B-C5FC5FC087C2 V1 EN
Figure 28:
Selecting the configuration mode
3.
On the
Composition code selection
page, select the correct composition codes
and click
Next
.
Ensure that the composition code is correct. PCM600 verifies
that the composition code matches the relay. If the composition
code digits related to the configuration, I/O or version do not
match the relay, PCM600 does not allow writing the
configuration to the relay. If other digits in the composition code
Section 4
1MRS759117 A
Setting up a project
52
REX640
Engineering Manual