7.3.3
Importing SCL files to PCM600
The IED engineering tool must be able to receive an SCD file or an ICD file as an
import to receive the engineered communication extensions, for example, for the
different IEDs.
To be able to import an SCD file at station level, the option IED 61850 configuration
engineering mode enabled has to be cleared in PCM600.
1.
On the
Tools
menu, select
Options
and click
IEC 61850 Configuration
.
2.
On the
Engineering
tab, clear the option
IED 61850 configuration
engineering mode enabled
and click
OK
.
GUID-3B18C93E-5450-43B1-823F-02C640D5FCB0 V1 EN
Figure 118:
Enabling SCD file import at station level
If the IED 61850 configuration engineering mode is enabled, SCD files cannot be
imported and an error message is shown.
GUID-F6D95B8F-7DBD-44A2-ABE7-39D8739B252E V1 EN
Figure 119:
Error message when SCD files cannot be imported
Section 7
1MRS759117 A
IEC 61850 communication engineering
140