3 2
3 2
100
=
<
×
I
I
IBase
EQUATION1520 V3 EN
(Equation 73)
where:
3I2
is the maximal negative sequence current during normal operating conditions, plus a margin of
10...20%
IBase
is the setting of base current for the function
9.2.3.4
Zero sequence based
The relay setting value
3U0>
is given in percentage of the global parameter
UBase
.
The setting of
3U0>
should not be set lower than according to equation
.
3 0
3 0
100
U
U
UBase
>=
×
EQUATION1521 V2 EN
(Equation 74)
where:
3U0
is the maximal zero sequence voltage during normal operation conditions, plus a margin of
10...20%
UBase is setting of global base voltage all functions in the IED.
The setting of the current limit
3I0<
is done in percentage of the global parameter
IBase
. The setting of
3I0<
must be higher than the normal unbalance current that
might exist in the system. The setting can be calculated according to equation
3 0
3 0
100
=
×
<
I
I
IBase
EQUATION2293 V2 EN
(Equation 75)
where:
3I0<
is the maximal zero sequence current during normal operating conditions, plus a margin of
10...20%
IBase
is setting of global base current all functions in the IED.
9.2.3.5
Delta U and delta I
Set the operation mode selector
OpDUDI
to
On
if the delta function shall be in
operation.
The setting of
DU>
should be set high (approximately 60% of
UBase
) and the current
threshold
DI<
low (approximately 10% of
IBase
) to avoid unwanted operation due to
1MRK 505 291-UEN A
Section 9
Secondary system supervision
177
Application manual
Summary of Contents for Relion REQ650
Page 1: ...Relion 650 series Breaker protection REQ650 Application manual ...
Page 2: ......
Page 20: ...14 ...
Page 26: ...20 ...
Page 48: ...42 ...
Page 82: ...76 ...
Page 90: ...84 ...
Page 160: ...154 ...
Page 178: ...172 ...
Page 264: ...258 ...
Page 288: ...282 ...
Page 302: ...296 ...
Page 330: ...324 ...
Page 338: ...332 ...
Page 339: ...333 ...