All the items that can be cleared are shown.
The content of the Clear menu depends on the configuration configured with PCM600.
2.
Select the item to be cleared with
or
.
3.
Press
, select OK to confirm the selection or Cancel to cancel the selection.
4.
To clear other items, repeat the steps.
6.3
Changing the IED functionality
6.3.1
Defining the setting group
GUID-A9853F1B-78ED-4AEF-AAE2-C27FF3DAE408 v3
Do not switch off the auxiliary power supply to the IED before changes. For
example, when setting parameter changes are saved.
6.3.1.1
Activating a setting group
AMU0600439 v8
IED settings are planned in advance for different operation conditions by calculating setting
values to different setting groups. The active setting group can be changed manually from the
menu or by the PCM600 tool.
1.
Select Main menu/Settings/Active setting group/SETGRPS:1 and press
.
IEC13000235-1-en.vsd
GUID-9BC3D595-CF08-42AF-B74E-0D3970A552DB V1 EN-US
Figure 36: Active setting group
2.
Select the setting group with
or
.
3.
Press
to confirm the selection or
to cancel.
4.
Commit the settings.
Remember to document the changes you make.
Section 6
1MRK 500 125-UEN A
Operating procedures
42
Operation manual