6.1.2.1
Creating disturbance recordings
GUID-B0CE46C1-1219-4BA2-9627-E53FC0413409 v5
Normally disturbance recordings are triggered by the IED applications but the recording can
also be triggered manually.
Set the DRPRDRE
Operation to On via LHMI or PCM600 and at least one channel
has to be connected. To make the setting, select Main menu/Settings/IED
Settings and then Monitoring/Disturbance report/DisturbanceReport/
DRPRDRE:1.
1.
Select Main menu/Disturbance records.
2.
Select Manual Trig with
or
.
3.
Press
to execute manual triggering.
IEC13000261-1-en.vsd
GUID-D18A9DC0-4392-4BAF-86D0-C43F2714B428 V1 EN-US
Figure 20: Manual triggering
The disturbance recorder is now triggered.
6.1.2.2
Monitoring disturbance recorder data
GUID-CBA8221F-A0F8-4043-98D7-577830F29F7F v6
Read individual disturbance recordings from the IED with the PCM600 software to monitor
disturbance recorder data.
1.
Select Main menu/Disturbance records.
All disturbance records are listed.
2.
Scroll the view with
or
.
Section 6
1MRK 500 125-UEN A
Operating procedures
32