Logic
Table 59. Tripping logic SMPPTRC
Function
Range or value
Accuracy
Trip action
3-ph, 1/3-ph, 1/2/3-ph
-
Minimum trip pulse length
(0.000-60.000) s
± 0.5% ± 10 ms
Timers
(0.000-60.000) s
± 0.5% ± 10 ms
Table 60. Configurable logic blocks
Logic block
Quantity with cycle time
Range or value
Accuracy
fast
medium
normal
LogicAND
60
60
160
-
-
LogicOR
60
60
160
-
-
LogicXOR
10
10
20
-
-
LogicInverter
30
30
80
-
-
LogicSRMemory
10
10
20
-
-
LogicRSMemory
10
10
20
-
-
LogicGate
10
10
20
-
-
LogicTimer
10
10
20
(0.000–90000.000) s
± 0.5% ± 10 ms
LogicPulseTimer
10
10
20
(0.000–90000.000) s
± 0.5% ± 10 ms
LogicTimerSet
10
10
20
(0.000–90000.000) s
± 0.5% ± 10 ms
LogicLoopDelay
10
10
20
(0.000–90000.000) s
± 0.5% ± 10 ms
Trip Matrix Logic
6
6
-
-
-
Boolean 16 to Integer 4
4
8
-
-
Boolean 16 to integer
with Logic Node
4
4
8
-
-
Integer to Boolean 16 4
4
8
-
-
Integer to Boolean 16
with Logic Node
4
4
8
-
-
Bay control REC670
1MRK511232-BEN E
Pre-configured
Product version: 1.2
ABB
57