Table 33. Sensitive directional residual overcurrent and power protection SDEPSDE
Function
Range or value
Accuracy
Operate level for 3I
0
·cos
j
directional residual
overcurrent
(0.25-200.00)% of
lBase
±
1.0% of I
r
at I
£
I
r
±
1.0% of I at I > I
r
At low setting:
(0.25-1.00)% of I
r
: ±0.05% of I
r
(1.00-5.00)% of I
r
: ±0.1% of I
r
Operate level for 3I
0
·3U
0
·
cos
j
directional residual
power
(0.25-200.00)% of
SBase
±
1.0% of S
r
at S
£
S
r
±
1.0% of S at S > S
r
At low setting:
(0.25-5.00)% of
SBase
±
10% of set value
Operate level for 3I
0
and
j
residual overcurrent
(0.25-200.00)% of
lBase
±
1.0% of I
r
at
£
I
r
±
1.0% of I at I > I
r
At low setting:
(0.25-1.00)% of I
r
: ±0.05% of I
r
(1.00-5.00)% of I
r
: ±0.1% of I
r
Operate level for non-
directional overcurrent
(1.00-400.00)% of
lBase
±
1.0% of I
r
at I
£
I
r
±
1.0% of I at I > I
r
At low setting <5% of I
r
:
±0.1% of I
r
Operate level for non-
directional residual
overvoltage
(1.00-200.00)% of
UBase
±
0.5% of U
r
at U
£
U
r
±
0.5% of U at U > U
r
Residual release current for
all directional modes
(0.25-200.00)% of
lBase
±
1.0% of I
r
at I
£
I
r
±
1.0% of I at I > I
r
At low setting:
(0.25-1.00)% of I
r
: ±0.05% of I
r
(1.00-5.00)% of I
r
: ±0.1% of I
r
Residual release voltage for
all directional modes
(0.01-200.00)% of
UBase
±
0.5% of U
r
at U
£
U
r
±
0.5% of U at U > U
r
Reset ratio
> 95%
-
Timers
(0.000-60.000) s
±
0.5%
±
10 ms
Inverse characteristics, see
table
19 curve types
Relay characteristic angle
RCA
(-179 to 180) degrees
±
2.0 degrees
Relay open angle ROA
(0-90) degrees
±
2.0 degrees
Operate time, non-directional
residual over current
60 ms typically at 0 to 2 x I
set
-
Bay control REC670
1MRK511232-BEN E
Pre-configured
Product version: 1.2
42
ABB