Table 30. Instantaneous residual overcurrent protection EFPIOC
Function
Range or value
Accuracy
Operate current
(1-2500)% of lBase
±
1.0% of I
r
at I
£
I
r
±
1.0% of I at I > I
r
Reset ratio
> 95%
-
Operate time
25 ms typically at 0 to 2 x I
set
-
Reset time
25 ms typically at 2 to 0 x I
set
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Operate time
10 ms typically at 0 to 10 x I
set
-
Reset time
35 ms typically at 10 to 0 x I
set
-
Critical impulse time
2 ms typically at 0 to 10 x I
set
-
Dynamic overreach
< 5% at
t
= 100 ms
-
Table 31. Four step residual overcurrent protection EF4PTOC
Function
Range or value
Accuracy
Operate current
(1-2500)% of
lBase
±
1.0% of I
r
at I
<
I
r
±
1.0% of I at I > I
r
Reset ratio
> 95%
-
Operate current for directional
comparison
(1–100)% of
lBase
±
1.0% of I
r
Timers
(0.000-60.000) s
±
0.5%
±
10 ms
Inverse characteristics, see table
18 curve types
and table
Second harmonic restrain
operation
(5–100)% of fundamental
±
2.0% of I
r
Relay characteristic angle
(-180 to 180) degrees
±
2.0 degrees
Minimum polarizing voltage
(1–100)% of
UBase
±
0.5% of U
r
Minimum polarizing current
(1-30)% of
IBase
±
0.25 % of I
r
Real part of source Z used for
current polarization
(0.50-1000.00)
W
/phase
-
Imaginary part of source Z used
for current polarization
(0.50–3000.00)
W
/phase
-
Operate time, start function
25 ms typically at 0 to 2 x I
set
-
Reset time, start function
25 ms typically at 2 to 0 x I
set
-
Critical impulse time
10 ms typically at 0 to 2 x I
set
-
Impulse margin time
15 ms typically
-
Bay control REC670
1MRK511232-BEN E
Pre-configured
Product version: 1.2
40