To navigate between the options, use
and
.
•
HMI menu paths are presented in bold, for example:
Select
Main menu/Settings
.
•
LHMI messages are shown in Courier font, for example:
To save the changes in non-volatile memory, select
Yes
and press
.
•
Parameter names are shown in italics, for example:
The function can be enabled and disabled with the
Operation
setting.
•
The ^ character in front of an input or output signal name in the function block
symbol given for a function, indicates that the user can set an own signal name
in PCM600.
•
The * character after an input or output signal name in the function block
symbol given for a function, indicates that the signal must be connected to
another function block in the application configuration to achieve a valid
application configuration.
1.4.3
Functions, codes and symbols
Table 1:
Functions included in 630 series IEDs
Functionality
IEC 61850
IEC 60617
ANSI
Protection
Three-phase non-directional overcurrent,
low stage
PHLPTOC
3I>
51P-1
Three-phase non-directional overcurrent,
high stage
PHHPTOC
3I>>
51P-2
Three-phase non-directional overcurrent,
instantaneous stage
PHIPTOC
3I>>>
50P/51P
Three-phase directional overcurrent, low
stage
DPHLPDOC
3I> →
67-1
Three-phase directional overcurrent, high
stage
DPHHPDOC
3I>> →
67-2
Non-directional earth-fault, low stage
EFLPTOC
I
0
>
51N-1
Non-directional earth-fault, high stage
EFHPTOC
I
0
>>
51N-2
Non-directional earth-fault, instantaneous
stage
EFIPTOC
I
0
>>>
50N/51N
Directional earth-fault, low stage
DEFLPDEF
I
0
> →
67N-1
Directional earth-fault, high stage
DEFHPDEF
I
0
>> →
67N-2
Transient/intermittent earth-fault
INTRPTEF
I
0
> → IEF
67NIEF
Stabilised restricted earth-fault
LREFPNDF
dI
0
Lo>
87NL
High-impedance–based restricted earth-
fault
HREFPDIF
dI
0
Hi>
87NH
Negative-sequence overcurrent
NSPTOC
I
2
>
46
Phase reversal
PREVPTOC
I
2
>>
46R
Three-phase thermal overload for feeder
T1PTTR
3Ith>F
49F
Table continues on next page
1MRS756801 A
Section 1
Introduction
630 series
7
Commissioning Manual