Functionality
IEC 61850
IEC 60617
ANSI
Three-phase thermal overload for
transformers
T2PTTR
3Ith>T
49T
Three-phase thermal overload for motors
MPTTR
3Ith>M
49M
Loss-of-load supervision
LOFLPTUC
3I<
37
Motor stall protection
JAMPTOC
Ist>
51LR
Emergency start
ESMGAPC
ESTART
ESTART
Motor start-up supervision
STTPMSU
Is2t n<
49,66,48,51LR
Negative phase-sequence time
overcurrent protection
MNSPTOC
I
2
>M
46M
Three-phase overvoltage
PHPTOV
3U>
59
Three-phase undervoltage
PHPTUV
3U<
27
Positive-sequence overvoltage
PSPTOV
U
1
>
47O+
Positive-sequence undervoltage
PSPTUV
U
1
<
47U+
Negative-sequence overvoltage
NSPTOV
U
2
>
47O-
Residual overvoltage
ROVPTOV
U
0
>
59G
Frequency gradient
DAPFRC
df/dt>
81R
Overfrequency
DAPTOF
f>
81O
Underfrequency
DAPTUF
f<
81U
Load shedding
LSHDPFRQ
UFLS/R
81LSH
Transformer differential protection for two-
winding transformers
TR2PTDF
3dI>T
87T
Fault locator
SCEFRFLO
FLOC
21FL
Distance protection
DSTPDIS
Z<
21, 21P, 21N
Automatic switch-onto-fault logic
CVRSOF
SOTF
SOTF
Phase discontinuity
PDNSPTOC
I
2
/I
1
>
46PD
Three-phase current inrush detection
INRPHAR
3I2f>
68
Circuit-breaker failure
CCBRBRF
3I>/I
0
>BF
51BF/51NBF
Autoreclosing
DARREC
O → I
79
Tripping logic
TRPPTRC
I → O
94/86
Protection-related functions
Local acceleration logic
DSTPLAL
LAL
LAL
Communication logic for residual
overcurrent
RESCPSCH
CLN
85N
Scheme communication logic
DSOCPSCH
CL
85
Current reversal and WEI logic
CRWPSCH
CLCRW
85CRW
Current reversal and WEI logic for
residual overcurrent
RCRWPSCH
CLCRWN
85NCRW
Control
Bay control
QCCBAY
CBAY
CBAY
Interlocking interface
SCILO
3
3
Circuit-breaker/disconnector control
GNRLCSWI
I ↔ O CB/DC
I ↔ O CB/DC
Table continues on next page
Section 1
1MRS756801 A
Introduction
8