Table 97. Synchrocheck (SYNCRSYN)
Characteristic
Value
Operation accuracy
At the frequency f = f
n
Voltage: ±1.0% or ±0.002 × U
n
Frequency: ±10 mHz
Phase angle ±2°
Reset time
<50 ms
Reset ratio
Typically 0.96
Operate time accuracy
+90ms/0 ms