Table 24. Electromagnetic compatibility tests
Description
Type test value
Reference
100 kHz and 1 MHz burst disturbance test
IEC 61000-4-18, level 3
IEC 60255-22-1
• Common mode
2.5 kV
• Differential mode
1.0 kV
3 MHz, 10 MHz and 30 MHz burst disturbance
test
IEC 61000-4-18
IEC 60255-22-1, class III
• Common mode
2.5 kV
Electrostatic discharge test
IEC 61000-4-2, level 4
IEC 60255-22-2
IEEE C37.90.3.2001
• Contact discharge
8 kV
• Air discharge
15 kV
Radio frequency interference tests
• Conducted, common mode
10 V (rms), f=150 kHz...80 MHz
IEC 61000-4-6 , level 3
IEC 60255-22-6
• Radiated, pulse-modulated
10 V/m (rms), f=900 MHz
ENV 50204
IEC 60255-22-3
• Radiated, amplitude-modulated
10 V/m (rms), f=80...2700 MHz
IEC 61000-4-3, level 3
IEC 60255-22-3
Fast transient disturbance tests
IEC 61000-4-4
IEC 60255-22-4, class A
• All ports
4 kV
Surge immunity test
IEC 61000-4-5, level 3/2
IEC 60255-22-5
• Communication
1 kV line-to-earth
• Binary inputs, voltage inputs
2 kV line-to-earth
1 kV line-to-line
• Other ports
4 kV line-to-earth, 2 kV line-to-line
Power frequency (50 Hz) magnetic field
IEC 61000-4-8
• 1...3 s
1000 A/m
• Continuous
300 A/m
Pulse magnetic field immunity test
1000 A/m
6.4/16 µs
IEC 61000-4-9
Damped oscillatory magnetic field immunity
test
IEC 61000-4-10
• 2 s
100 A/m
• 1 MHz
400 transients/s
Power frequency immunity test
Binary inputs only
IEC 60255-22-7, class A
IEC 61000-4-16
• Common mode
300 V rms
• Differential mode
150 V rms
Conducted common mode disturbances
15 Hz...150 kHz
Test level 3 (10/1/10 V rms)
IEC 61000-4-16
Generator Protection and Control
1MRS757583 C
REG630
Product version: 1.3