Table 24. Electromagnetic compatibility tests, continued
Description
Type test value
Reference
Voltage dips and short interruptions
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
IEC 61000-4-11
Electromagnetic emission tests
EN 55011, class A
IEC 60255-25
• Conducted, RF-emission (mains terminal)
0.15...0.50 MHz
<79 dB(µV) quasi peak
<66 dB(µV) average
0.5...30 MHz
<73 dB(µV) quasi peak
<60 dB(µV) average
• Radiated RF-emission
30...230 MHz
<40 dB(µV/m) quasi peak, measured at 10 m
distance
230...1000 MHz
<47 dB(µV/m) quasi peak, measured at 10 m
distance
Table 25. Insulation tests
Description
Type test value
Reference
Dielectric tests
IEC 60255-5
IEC 60255-27
• Test voltage
2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1 min, communication
Impulse voltage test
IEC 60255-5
IEC 60255-27
• Test voltage
5 kV, 1.2/50 μs, 0.5 J
1 kV, 1.2/50 μs, 0.5 J, communication
Insulation resistance measurements
IEC 60255-5
IEC 60255-27
• Isolation resistance
>100 MΩ, 500 V DC
Protective bonding resistance
IEC 60255-27
• Resistance
<0.1Ω, 4 A, 60 s
Table 26. Mechanical tests
Description
Reference
Requirement
Vibration tests (sinusoidal)
IEC 60068-2-6 (test Fc)
IEC 60255-21-1
Class 1
Shock and bump test
IEC 60068-2-27 (test Ea shock)
IEC 60068-2-29 (test Eb bump)
IEC 60255-21-2
Class 1
Seismic test
IEC 60255-21-3 (method A)
Class 1
Generator Protection and Control
1MRS757583 C
REG630
Product version: 1.3
24
ABB