72
1MRS 750616-MUM
Directional or Non-Directional Earth-Fault Relay
Technical Reference Manual
REJ 527
Table 9.-3 Control parameters
Variable
Parameter
Setting range
Default
setting
Customer’s
setting
Rated frequency
V133
50/60
50
Nominal voltage
V134
100/110/115/120 100
Remote control of settings
V150
0/1
0
Non-volatile memory settings
V152
0...31
31
Event mask for I
0
> , U
0
> and U
0b
> V155
0...255
85
Event mask for I
0
>> and U
0
>>
V156
0...15
5
Event mask for output contacts’
events
V157
0...255
3
Event mask for the disturbance
recorder and the HMI password
V158
0...7
1
Unit address of the relay
V200
1...254
1
Data transfer rate
V201
4.8 or 9.6 kbps
9.6
Operate time of the CBFP
S121
0.10...1.00 s
0.10
Time setting for disabling new trip
indications on the LCD
S122
0...999 min
60
Table 9.-4 Parameters for the disturbance recorder
Information
Parameter
Setting range
Default
setting
Customer’s
setting
Post-triggering recording length in
percent
V240
0...100%
50%
Internal trigger signals’ checksum V241
0...63
8
Internal trigger signal’s edge
V242
0...63
0
External trigger signal (BI)
V243
0/1
1
External trigger signal’s edge
V244
0/1
0
Sampling rate
M15
800/960 Hz
400/480 Hz
50/60 Hz
800/960
Hz
Station identification/unit number
M18
0…9999
0000
Station name
M20
Max 15
characters
- ABB -
Analogue channel: rated voltage
and unit of primary voltage
transformer
M80
Rated voltage
0.00...600;
unit V or kV
0.00,kV
Analogue channel: conversion
factor and unit, I
0
M81
Factor 0…65535;
unit A or kA
00000, A
Summary of Contents for REJ 527