1MRS 750616-MUM
Directional or Non-Directional Earth-Fault Relay
Technical Reference Manual
REJ 527
49
Explanations of the default values:
0 = not included in the event reporting
1 = included in the event reporting
Events E50 and E51 are always included in the event reporting.
4.1.9.4.
SPA bus communication protocol parameters
In some cases, altering parameter values via serial communication requires the use
of the SPA password. The password is a number within the range 1...999, the default
value being 1.
To enter the setting mode, enter the password into parameter V160. To quit the
setting mode, enter the same password into parameter V161. The password
protection is also reactivated in case of loss of auxiliary voltage.
The HMI password can be changed via parameter V162, but it is not possible to read
the password via this parameter.
Abbreviations used in the following tables:
• R = readable data
• W = writeable data
• P = password protected writeable data
• I = input data
Table 4.1.9.3-4
Event codes E13…E20
Code
Event
Weighting factor
Default value
E13
PO1 activated
1
1
E14
PO1 reset
2
1
E15
PO2 activated
4
0
E16
PO2 reset
8
0
E17
SO1 activated
16
0
E18
SO1 reset
32
0
E19
SO2 activated
64
0
E20
SO2 reset
128
0
Default value of event mask V157
3
Table 4.1.9.3-5
Event codes E31...E33
Code
Event
Weighting factor
Default value
E31
Disturbance recorder triggered
1
1
E32
HMI password opened
2
0
E33
HMI password reclosed
4
0
Default value of event mask V158
1
Table 4.1.9.3-6
Event codes E50 and E51
Code
Event
E50
Restart of relay
E51
Overflow of event register