1MRS 750616-MUM
Directional or Non-Directional Earth-Fault Relay
Technical Reference Manual
REJ 527
71
Table 9.-2 Setting group 2
Variable
Group 2
(R, W, P)
Setting range
Default
setting
Customer’s
setting
Set start value of stage I
0
>
S81
1.0...100% x I
n
1.0% x I
n
Set start value of stage U
0
>
S82
2.0...80.0% x U
n
2.0% x U
n
Operate time of stage I
0
>/U
0
>
S83
0.10...300 s
0.10 s
Time multiplier k of stage I
0
>
S84
0.05...1.00
0.05
Set start value of stage I
0
>>
S85
5.0...400% x I
n
5.0% x I
n
Set start value of stage U
0
>>
S86
2.0...80.0% x U
n
2.0% x U
n
Operate time of stage I
0
>>/
U
0
>>
S87
0.10...300 s
0.10 s
Set start value of stage U
0b
>
S88
2.0...80.0% x U
n
2.0% x U
n
Operate time of stage U
0b
>
S89
0.10...300 s
0.10 s
Additional angle (
ϕ
a
) of stage
I
0
>/I
0
>> with the basic angle
S90
0...90
°
0
°
Basic angle (
ϕ
b
) of stage I
0
>/
I
0
>>
S91
-90...0
°
-90
°
Angle correction
(ϕ
c
) of stage
I
0
>/ I
0
>> with the I
ϕ
characteristic
S92
2...7
°
2
°
Checksum, SGF1
S93
0...31
0
Checksum, SGF2
S94
0...255
0
Checksum, SGF3
S95
0...255
0
Checksum, SGF4
S96
0...32
0
Checksum, SGF5
S97
0...4
0
Checksum, SGB1
S98
0...255
0
Checksum, SGR1
S99
0...15
12
Checksum, SGR2
S100
0...15
3
Checksum, SGR3
S101
0...15
12
Checksum, SGR4
S102
0...15
3
Checksum, SGR5
S103
0...15
12
Checksum, SGR6
S104
0...15
3