46
R E F61 5 A N S I 5.0 FP1
FEED ER P R OT EC T I O N A N D CO N T R O L
—
Table 41. Wattmetric-based earth-fault protection (WPWDE) main settings
Parameter
Function
Value (range)
Step
Directional mode
WPWDE
2 = Forward
3 = Reverse
-
Current start value
WPWDE
0.010...5.000 × I
n
0.001
Voltage start value
WPWDE
0.010...1.000 × U
n
0.001
Power start value
WPWDE
0.003...1.000 × P
n
0.001
Reference power
WPWDE
0.050...1.000 × P
n
0.001
Characteristic angle
WPWDE
-179...180°
1
Time multiplier
WPWDE
0.05...2.00
0.01
Operating curve type
1)
WPWDE
Definite or inverse time
Curve type: 5, 15, 20
Operate delay time
WPWDE
60...200000 ms
10
Min operate current
WPWDE
0.010...1.000 × I
n
0.001
Min operate voltage
WPWDE
0.01...1.00 × U
n
0.01
—
Table 42. Transient/intermittent earth-fault protection (INTRPTEF)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2 Hz
±1.5% of the set value or ±0.002 × Uo
Operate time accuracy
±1.0% of the set value or ±20 ms
Suppression of harmonics
-50 dB at f = n × fn, where n = 2,3,4,5,…
—
Table 43. Transient/intermittent earth-fault protection (INTRPTEF) main settings
Parameter
Function
Value (range)
Step
Directional mode
INTRPTEF
1 = Non-directional
2 = Forward
3 = Reverse
-
Operate delay time
INTRPTEF
40...1200000 ms
10
Voltage start value
INTRPTEF
0.05...0.50 × U
n
0.01
Operation mode
INTRPTEF
1 = Intermittent EF
2 = Transient EF
-
Peak counter limit
INTRPTEF
2...20
1
Min operate current
INTRPTEF
0.01...1.00 × I
n
0.01
—
Table 44. Harmonics-based earth-fault protection (HAEFPTOC)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2 Hz
±5% of the set value or ±0.004 × I
n
Start time
1), 2)
Typically 77 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Operate time accuracy in IDMT mode
3)
±5.0% of the set value or ±20 ms
Suppression of harmonics
-50 dB at f = fn
-3 dB at f = 13 × fn
1) Fundamental frequency current = 1.0 × I
n
, harmonics current before fault = 0.0 × I
n
, harmonics fault current 2.0 × Start value , results based on statistical distribution of 1000 mea
-
surements
2) Includes the delay of the signal output contact
3) Maximum Start value = 2.5 × I
n
, Start value multiples in range of 2...20