20
R E F61 5 A N S I 5.0 FP1
FEED ER P R OT EC T I O N A N D CO N T R O L
—
Figure 9. Application ex-
ample with single busbar
switchgear arranged into
two bus sections sepa-
rated with bus coupler
In the application example in Figure 9, a single bus
bar switchgear is arranged into two bus sections
separated with bus coupler. Standard configura-
tion F is used in the outgoing feeders with optional
Arc Flash detection for increased safety. The syn-
chro-check and voltage remnant functions are used
in standard configuration N in the incoming feed-
ers, and configuration P in the tie breaker. Standard
configuration P has 6 voltage inputs to be able to
monitor decaying voltage in the buses for the im-
plementation of Automatic Transfer Schemes.