R E F61 5 A N S I 5.0 FP1
FEED ER P R OT EC T I O N A N D CO N T R O L
—
Table 59. Negative-sequence overvoltage protection (NSPTOV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±1.5% of the set value or ±0.002 × U
n
Start time
1) 2)
Minimum
Typical
Maximum
U
Fault
= 1.1 x set Start value
U
Fault
= 2.0 x set Start value
33 ms
24 ms
35 ms
26 ms
37 ms
28 ms
Reset time
Typically 40 ms
Reset ratio
Typically 0.96
Retardation time
< 35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,…
1) Negative-sequence voltage before fault = 0.0 × U
n
, f
n
= 50 Hz, negative-sequence overvoltage with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
—
Table 60. Negative-sequence overvoltage protection (NSPTOV) main settings
Parameter
Function
Value (range)
Step
Start value
NSPTOV
0.010...1.000 × U
n
0.001
Operate delay time
NSPTOV
40...120000 ms
1
—
Table 61. Frequency protection (FRPFRQ)
Characteristic
Value
Operation accuracy
f>/f<
±5 mHz
df/dt
±50 mHz/s (in range |df/dt| <5 Hz/s)
±2.0% of the set value (in range 5 Hz/s < |df/dt| < 15 Hz/s)
Start time
1) 2)
f>/f<
<80 ms
df/dt
<120 ms
Reset time
<150 ms
Operate time accuracy
±1.0% of the set value or ±30 ms
—
Table 58. Positive-sequence undervoltage protection (PSPTUV) main settings
Parameter
Function
Value (range)
Step
Start value
PSPTUV
0.010...1.200 × U
n
0.001
Operate delay time
PSPTUV
40...120000 ms
10
Voltage block value
PSPTUV
0.01...1.00 × U
n
0.01
—
Table 57. Positive-sequence undervoltage protection (PSPTUV)
Characteristic
Value
Operation accuracy
Depending on the frequency of the measured current: f
n
±2 Hz
±1.5% of the set value or ±0.002 x I
n
Start time
1) 2)
Minimum
Typical
Maximum
U
Fault
= 0.99 x set Start value
U
Fault
= 0.9 x set Start value
52 ms
44 ms
55 ms
47 ms
58 ms
50 ms
Reset time
Typically 40 ms
Reset ratio
Depends on the set Relative hysteresis
Retardation time
< 35 ms
Operate time accuracy in definite time mode
±1.0% of the set value or ±20 ms
Suppression of harmonics
DFT: -50dB at f = n x f
n
, where n = 2, 3, 4, 5,…
1) Start value = 1.0 × U
n
, positive-sequence voltage before fault = 1.1 × U
n
, f
n
= 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results
based on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact