cos
test
test
Tinv
kSN Sref
I
U
j
=
×
×
×
IECEQUATION2403 V1 EN
(Equation 2)
6.
Compare the result with the expected value.
The expected value depends on whether definite or inverse time was selected.
7.
Continue to test another function or complete the test by setting the test mode
to
Off
.
Operation mode 3I
0
and φ
1.
Set the polarizing voltage to 1.2 ·
UNRel>
and the phase angle between
voltage and current to the set characteristic angle (
RCADir
), the current
lagging the voltage.
2.
Measure that the operate power is equal to the
INDir>
setting for the set
directional element.
Note that for operation, both the injected current and voltage
must be greater than the set values
INRel>
and
UNRel>
respectively.
The function activates the START and STDIRIN output.
3.
Measure with angles
j
around
/- ROADir.
4.
Compare the result with the set values, refer to figure
characteristic.
5.
Measure the operate time of the timer by injecting a current to get two times
the set
SN>
operate value.
( )
0
0
/ 3
3
cos
test
test
Tinv
kSN Sref
I
U
j
=
×
×
×
IECEQUATION2403 V1 EN
(Equation 3)
6.
Compare the result with the expected value.
The expected value depends on whether definite or inverse time was selected.
7.
Continue to test another function or complete the test by setting the test mode
to
Off
.
1MRK 511 248-UEN -
Section 6
Testing functionality
47