![ABB REC650 ANSI Commissioning Manual Download Page 44](http://html1.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_commissioning-manual_3388517044.webp)
Apply input signals as needed according to the actual hardware and
the application configuration made in PCM600.
1.
Inject a symmetrical three-phase voltage and current at rated value.
2.
Compare the injected value with the measured values.
The voltage and current phasor menu in the local HMI is located under
Main
menu/Measurements/Analog primary values
and
Main menu/
Measurements/Analog secondary values
.
3.
Compare the frequency reading with the set frequency and the direction of the
power.
The frequency and active power are located under
Main menu/Tests/
Function status/Monitoring/CVMMXN/1:CVMMXN/Outputs
. Then
navigate to the bottom of the list to find the frequency.
Check both analog primary and secondary values, because
then the CT and VT ratios entered into the IED are also checked.
These checks shall be repeated for Analog primary values.
4.
Inject an unsymmetrical three-phase voltage and current, to verify that phases
are correctly connected.
If some setting deviates, check the analog input settings under
Main menu/Configuration/Analog modules
Measured values such as current and voltages as well as active, reactive and
apparent power, power factor phase angles as well as positive and negative and
zero sequence currents and voltages are available in the local HMI under
Main
menu/Tests/Function status/Monitoring
.
Navigate to the measurement function that contains the quantity to be checked.
Table 1:
Measurement functions
Function
Quantity
Description
CMMXU
IL1 to IL3
amplitude, range and angle
CMSQI
3I
0
; I1 and I2
amplitude, range and angle
CVMMXN
S; P; Q; PF; Ilag; Ilead; U; I and
f
amplitude, range and angle
VMMXU
UL12 to UL31 i.e. phase-to-
phase
amplitude, range and angle
VMSQI
3U
0
; U1 and U2
amplitude, range and angle
VNMMXU
UL1 to UL3 i.e. phase-to-neutral amplitude, range and angle
Section 5
1MRK 511 248-UEN -
Testing IED operation
36
Commissioning Manual