![ABB REC650 ANSI Commissioning Manual Download Page 54](http://html1.mh-extra.com/html/abb/rec650-ansi/rec650-ansi_commissioning-manual_3388517054.webp)
-3U
0
=U
ref
Operate area
Instrument
transformer
angle error
3I
0
(prim)
3I
0
(to prot)
a
Characteristic after
angle compensation
RCAcomp
en06000651.vsd
RCADir
= 0º
IEC06000651 V2 EN
Figure 10:
Explanation of RCAcomp
Operation mode 3I
0
· 3U
0
· cosφ
1.
Set the polarizing voltage to 1.2 ·
UNRel>
and the phase angle between
voltage and current to the set characteristic angle (
RCADir
), the current
lagging the voltage.
2.
Measure that the operate power is equal to the
SN>
setting for the set
directional element.
Note that for operation, both the injected current and voltage must be greater
than the set values
INRel>
and
UNRel>
respectively.
The function activates the START and STDIRIN outputs.
3.
Measure with angles
j
=
RCADir
+/- 45° that the measuring element operates
when 3I
0
· 3U
0
· cos (
RCADir
-
j
) = 3I0 · 3U0 · cos(+/-45) =
SN>
.
4.
Compare the result with the set value. Take the set characteristic into
consideration, see figure
and figure
.
5.
Measure the operate time of the timer by injecting 1.2 ·
UNRel>
and a current
to get two times the set
SN>
operate value.
Section 6
1MRK 511 248-UEN -
Testing functionality
46
Commissioning Manual