IEC09000357-1-en.vsd
IEC09000357 V1 EN
Figure 5:
Select the TCP/IP protocol and open Properties
4. Select
Obtain an IP address automatically
if the parameter
DHCPServer
is
set to
On
in the IED.
IEC09000358-1-en.vsd
IEC09000358 V1 EN
Figure 6:
Select: Obtain an IP address automatically
5. Select
Use the following IP address
and define
IP address
and
Subnet mask
if
the front port is used and if the
IP address
is not set to be obtained
automatically by the IED, see
. The IP address must be different from
the IP address chosen for the IED.
Section 3
1MRK 511 248-UEN -
Starting up
24