5 - Installation
2QFHWKHSKDVHRIPHFKDQLFDOLQVWDOODWLRQRIWKH0(7(5LV¿QLVKHG
LWLVQHFHVVDU\WRFRQ¿JXUHWKH0(7(5LQRUGHUWRPDNHLWFRPSDWLEOH
with the REACT2 system. Set the parameters of the meter as set out
in the table:
Parameter
Settings
Address
1
Protocol
MODBUS
Baud rate
19200
Parity
EVEN
The settings are made by using the keypad and the display on the meter:
1. Press for two seconds to access the setup menu of the meter.
2. Press repeatedly until the display shows “
Set
”.
- Press
WRFRQ¿UP
3. Press repeatedly until the display shows “
RS-485
”.
- Press
WRFRQ¿UP
4. Press repeatedly until the display shows “
Protocol
”.
- Press to access.
- Press
to enable the change in the value.
- Press repeatedly until the display shows “
Modbus
”.
- Press
WRFRQ¿UPWKHFKDQJH
- Press for two seconds to return to the RS485 menu.
5. Press repeatedly until the display shows “
Baud rate
”.
- Press to access.
- Press
to enable the change in the value.
- Press repeatedly and select 19200.
- Press
WRFRQ¿UPWKHFKDQJH
- Press for two seconds to return to the RS485 menu.
6. Press repeatedly until the display shows “
Address
”.
- Press to access.
- Press
to enable the change in the value.
- Press repeatedly and select 1.
- Press
WRFRQ¿UPWKHFKDQJH
- Press for two seconds to return to the RS485 menu.
7. Press repeatedly until the display shows “
Modbus
”.
- Press to access.
- Press
to enable the change in the value.
- Press repeatedly and select even.
- Press
WRFRQ¿UPWKHFKDQJH