5 - Installation
I
nstalling the ground cable(s)
Connect the ground cables of the DC side to the equipment grounding
conductor terminal (EGC)
16
.
EGC connection point accept a ring cable lug, suitable for a M6 size
threaded insert (torque to 11Nm/8ft-lb)
Attach the AC side ground cable to the protective earth (PE) connection
point
37
.
T
he protective earth (PE) connection point accept a ring cable lug, suitable
for a M6 size threaded insert (torque to 11Nm/8ft-lb).