8 - Maintenance
6. Operations on Internal DC disconnect switch(if present)
15
•
Open the internal DC switch
15
(blue in the below picture).
•
Affix designated lock preventing operation onto DC disconnect
switch
15
, affixing designated tags (LOTO procedure).
•
Check on the status LEDs
05
the shutdown command has been
carried out (Missing DC voltage status):
All LEDs OFF
.
The time needed for the complete shut-down of the LEDs depends by the input voltage of the
inverter. The complete shut-down of the LEDs may require some minutes.