3 - Characteristics
P
rincipal inverter components
• DC disconnect switch
15
PVS-60-TL(-R)-US all versions
Model: OTDC180U22 or equivalent
DC disconnect switch
Voltage
Utilization category
Current
1000Vdc
DC-21B
150A (50A for each pole)
• String fuses
34
35
PVS-60-TL(-R)-US -S/-SC version
The standard string protection fuses installed on the inverter have the
following features:
Voltage
Rating
Type
1000Vdc
15 A (Max. Rating 20A)
gPV
• DC overvoltage surge arresters
32
class 2
PVS-60-TL(-R)-US all versions
The DC overvoltage surge arresters installed on these inverter models are:
Brand:PTG
Model: PV600-40M2-M(5 elements)
These components are not replaceable
• AC overvoltage surge arresters
36
class 2
PVS-60-TL(-R)-US all versions
The AC overvoltage surge arresters installed on these inverter models are:
Brand:PTG
Model: PTE 385-40M2-10 (4 elements)
These components are not replaceable