23
USER M A N UA L
03: Voltage range for bypass
Interface
Settings
Parameter 2:
Set the acceptable low voltage for bypass. Setting range is
from 110V to 209V and the default value is 110V.
Parameter 3:
Set the acceptable high voltage for bypass. Setting range
is from 231V to 276V and the default value is 264V.
04: Frequency range for bypass
Interface
Settings
Parameter 2:
Set the acceptable low frequency for bypass.
50 Hz system: Setting range is from 46.0Hz to 49.0Hz.
60 Hz system: Setting range is from 56.0Hz to 59.0Hz.
The default value is 46.0Hz/56.0Hz.
Parameter 3:
Set the acceptable high frequency for bypass.
50 Hz: Setting range is from 51.0Hz to 54.0 Hz.
60 Hz: Setting range is from 61.0Hz to 64.0Hz.
The default value is 54.0Hz/64.0Hz.
05: Reserved
Interface
Settings
Reserved
06: Reserved
Interface
Settings
Reserved
07: Reserved
Interface
Settings
Reserved
08: Bypass mode setting
Interface
Settings
Parameter 2:
OPN:
Bypass allowed. When selected, UPS will run at Bypass mode
depending on bypass enabled/disabled setting.
FBD:
Bypass not allowed. When selected, it’s not allowed for running in
Bypass mode under any situations.
Parameter 3:
ENA:
Bypass enabled. When selected, Bypass mode is activated.
DIS:
Bypass disabled. When selected, automatic bypass is acceptable, but
manual bypass is not allowed. Manual bypass means users manually operate
UPS for Bypass mode. For example, pressing OFF button in AC mode to turn
into Bypass mode.