background image

16

POWERVALUE 11T IN — 

6-10 KVA

4. Operation

This chapter describes how the UPS is operated 
through the LCD.
The user can:
•  Operate the LCD
•  Start up and shut down the UPS  

(excluding the commissioning start up)

•  Operate additional SNMP adapters and  

their software

4 .1 Control panel

The user-friendly control panel has two parts:
•  Selection keys
•  Power management LCD (PMD)

Table 2: UPS selection keys

Button

Function

Illustration

 

ON/Enter

ON/Enter
button

•   Turn on the UPS: Press and hold the button more than 1s to turn on the UPS.
•   Enter key: Press this button to confirm the selection in setting menu.

 

OFF/ESC

OFF/ESC
button

•   Turn off the UPS: Press and hold the button more than 1s to turn off the UPS.
•   Esc key: Press this button to return to last menu in setting menu.

 

Test/Up

Test/Up
button

•   Battery test: Press and hold the button more than 1s to test the battery while in AC mode, 

or CVCF mode.

•   UP key: Press this button to display next selection in setting menu.

 

Mute/Down

Mute/Down
button

•   Mute the alarm: Press and hold the button more than 1s to mute the buzzer. Please refer to 

section 3-4 “Mute the buzzer” for details.

•   Down key: Press this button to display previous selection in setting menu.

 

Test/Up

 

Mute/Down

Test/Up +
Mute/Down
button

•   Press and hold the two buttons simultaneous more than 1s to enter/escape the setting 

menu.

4.1.1 Selection keys

The user-friendly control 
panel has two parts:
•  Selection keys
•  Power management LCD 

(PMD)


4.1-1
Control panel

Selection

keys

LCD

Summary of Contents for PowerValue 11T IN

Page 1: ... USER MANUAL PowerValue 11T IN 6 10 kVA ...

Page 2: ......

Page 3: ...tentially dangerous situation Failure to observe may cause injury death or equipment damage This symbol in conjunction with the signal word NOTE indicates operator tips or particularly useful or important information for the use of the product This symbol and wording do not indicate a dangerous situation This symbol indicates that reading the instruction manual booklet before starting work or befo...

Page 4: ...6 Connection warnings 1 7 Operation 2 Maintenance 9 10 2 1 UPS disposal and recycling 2 1 1 For professional users in the European Union 2 1 2 For disposal in countries outside of the European Union 3 Installation 11 15 3 1 Delivery transportation positioning and storage 3 1 2 Unpacking list 3 1 3 Operation of UPS 3 1 4 Storage of UPS 3 2 General characteristics 3 2 1 Front panel 3 2 2 Rear panel ...

Page 5: ... UPS operation 4 4 LCD wordings index 4 5 LCD panel 4 6 LCD settings 5 Communication 26 5 1 RS 232 port 5 2 USB port 5 3 Emergency power off 6 Troubleshooting 27 29 6 1 Fault identification and rectification 6 2 Accessing alarms 6 2 1 Faults reference code 6 2 2 Warning indicator 6 2 3 Audible alarm 6 2 4 Troubleshooting ...

Page 6: ...nual Excessive amounts of dust or moisture in the operating environment may cause damage or lead to malfunction The UPS should always be protected from the weather and sunshine The operating environment must meet the weight airflow size and clearance requirements specified in the technical datasheet Under no circumstances should the UPS be installed in an airtight room in the presence of flammable...

Page 7: ...ING Do not connect appliances or devices which would overload the UPS e g big motor type equipment to the UPS output sockets or terminal WARNING Place cables in such a way that no one can step on or trip over them WARNING Do not block air vents in the housing of UPS The UPS must be installed in a location with good ventilation Ensure enough space on each side for ventilation WARNING UPS is provide...

Page 8: ...a grounding electrode conductor The UPS is connected to a DC energy source battery The output terminals may be live when the UPS is not connected to an AC supply Before working on this circuit Isolate Uninterruptible Power System UPS Then check for hazardous voltage between all terminals including the protective earth DANGER Risk of voltage backfeed 1 7 Operation WARNING Do not disconnect the main...

Page 9: ...f batteries in a fire the batteries may explode WARNING Do not open or mutilate batteries Released electrolyte is harmful to the skin and eyes It may be toxic DANGER Components inside the UPS are connected to the battery even when the UPS is disconnected from the mains power supply DANGER Disconnect the batteries before carrying out any kind of service and or maintenance Verify that no current is ...

Page 10: ...ffects on human health and the environment which could otherwise arise from inappropriate waste handling 2 1 UPS disposal and recycling 2 1 1 For professional users in the European Union The crossed out wheeled bin symbol on the product s and or accompanying documents means that used electrical and electronic equipment WEEE should not be mixed with general household waste If you wish to discard el...

Page 11: ...EC C19 cable only for 2KB 2KS 3KB 3KS 1 x external battery cable only for S models 1 x USB cable 1 x fixing plate for battery cable Examine the UPS for any signs of damage and ensure that the received UPS corresponds to the material indicated in the delivery note Notify your carrier or supplier immediately in case of any damage 3 1 3 Operation of UPS The UPS system contains no user serviceable par...

Page 12: ...l characteristics 3 2 1 Front panel Figure 3 3 1 1 shows the front panel of the UPS PowerValue 11T 6KL 10KL PowerValue 11T 6K 10K 3 2 1 1 PowerValue 11T UPS front panel PowerValue 11T 6K 10K 3 2 1 2 PowerValue 11T External battery front panel ...

Page 13: ... panel The figures below show the connectors and ports in the UPS and external battery module rear panel 3 2 2 1 PowerValue 11T 6kVA 10kVA rear view 3 2 2 2 PowerValue 11T 6kVA 10kVA rear view 3 2 2 3 External battery rear view ...

Page 14: ... the following table Model Wiring spec AWG Input Output Battery Ground 6KB 10 12 12 6KS 10 12 12 12 10KB 8 8 8 10KS 8 8 8 8 NOTE It is recommended to use suitable wire in above table or thicker for safety and efficiency NOTE The selections for color of wires should be followed by the local electrical laws and regulations 5 Cabinet placement Secure the UPS to the ground with two shipping brackets A...

Page 15: ...rd battery pack there are one DC breaker to disconnect the battery pack and the UPS But for other external battery pack make sure a DC breaker or other protection device between UPS and external battery pack is installed If not please install it carefully Switch off the battery breaker before installation NOTE Set the battery pack breaker in OFF position and then install the battery pack Pay high ...

Page 16: ...Press and hold the button more than 1s to turn off the UPS Esc key Press this button to return to last menu in setting menu Test Up Test Up button Battery test Press and hold the button more than 1s to test the battery while in AC mode or CVCF mode UP key Press this button to display next selection in setting menu Mute Down Mute Down button Mute the alarm Press and hold the button more than 1s to ...

Page 17: ... of alarms UPS condition Buzzer status Active fault Continuous Active warning Beep every second Battery UPS on battery Beep every 4 seconds Low battery Buzzer beeps every second Bypass Beep every 10 minutes Overload Beep twice every second The status screen shows the following information Status summary including operating mode and load information Alarm status if present including fault and warni...

Page 18: ...ge battery under this mode Battery mode When the input voltage is beyond the acceptable range or power failure UPS will backup power from battery and alarm will beep every 4 seconds Bypass mode When input voltage is within acceptable range and bypass is enabled turn off the UPS and it will enter Bypass mode Alarm beeps every two minutes Battery test When UPS is in AC mode or CVCF mode press Test k...

Page 19: ... is at low level and the UPS will shut down automatically soon Users could switch off some non critical loads to disable the shutdown alarm and prolong the backup time If there is no more load to be switched off at that time you have to shut down all loads as soon as possible to protect the devices or save data Otherwise there is a risk of data loss or power failure 2 In Battery mode if buzzer sou...

Page 20: ... in chapter 4 for details 2 Please check the loads wiring ventilation utility battery and so on after the fault occurs Don t try to turn on the UPS again before solving the problems If the problems can t be fixed please contact the distributor or service people immediately 3 For emergency case please cut off the connection from utility external battery and output immediately to avoid more risk or ...

Page 21: ...c battery voltage Hz frequency Indicates the load level by 0 25 26 50 51 75 and 76 100 Indicates overload Indicates the load or the UPS output is short circuit Indicates the UPS connects to the mains Indicates the battery is working Indicates the bypass circuit is working Indicates the inverter circuit is working Indicates the output is working Indicates the battery capacity by 0 25 26 50 51 75 an...

Page 22: ...2 Output frequency Setting the output frequency You may choose following three options in parameter 2 50 0Hz The output frequency is setting for 50 0Hz 60 0Hz The output frequency is setting for 60 0Hz ATO If selected output frequency will be decided according to the latest normal utility frequency If it is from 46Hz to 54Hz the output frequency will be 50 0Hz If it is from 56Hz to 64Hz the output...

Page 23: ...0 Hz Setting range is from 51 0Hz to 54 0 Hz 60 Hz Setting range is from 61 0Hz to 64 0Hz The default value is 54 0Hz 64 0Hz 05 Reserved Interface Settings Reserved 06 Reserved Interface Settings Reserved 07 Reserved Interface Settings Reserved 08 Bypass mode setting Interface Settings Parameter 2 OPN Bypass allowed When selected UPS will run at Bypass mode depending on bypass enabled disabled set...

Page 24: ... Interface Settings Reserved 11 Reserved Interface Settings Reserved 12 Reserved Interface Settings Reserved 13 Battery voltage calibration Interface Settings Parameter 2 Select Add or Sub function to calibrate battery voltage to real figure Parameter 3 The voltage setting range is from 0V to 5 7V The default value is 0V 14 Reserved Interface Settings Reserved 15 Inverter voltage calibration Inter...

Page 25: ...del and 1A for standard model The available options are 1A 2A 4A and 6A 6A is only available for the UPS with 16 pieces of batteries 19 Battery capacity and groups setting Interface Settings Parameter 2 Set the battery capacity such as 7AH 9AH 10AH 12AH 17AH 26AH 40AH 65AH 100AH and so on The default value is 9AH Parameter 3 Set battery group range from 1 to 6 The default value is 1 group These pa...

Page 26: ...the other end to the RS 232 port of a computer The cable pins for the RS 232 communication port are described in Figure 5 1 1 and Table 7 5 1 1 RS 232 Communication Port DB 9 Connector Table 7 Communication port pin assignment PIN Signal name Function Direction from UPS 2 TxD Transmit to external device Out 3 RxD Receive from external device in 5 GND Signal common 5 2 USB port The UPS can communic...

Page 27: ...of power to the load 6 2 Accessing alarms 6 2 1 Faults reference code Fault event Fault code Icon Bus start fail 01 X Bus over 02 X Bus under 03 X Bus unbalance 04 X Inverter soft start failure 11 X High Inverter voltage 12 X 6 2 2 Warning indicator Warning Icon flashing Code Alarm Low battery Sounding every second Overload Sounding twice every second Battery unconnected Sounding every second Over...

Page 28: ...very second Charger failure Beeping once every second Overload 3 times in 30min Beeping once every second EPO status Beeping once every second Cover of maintain switch is open Beeping once every second Fault Alarm Muted Bus start failure Beeping continuously Yes Bus over Beeping continuously Bus under Beeping continuously Bus unbalance Beeping continuously Inverter soft start failure Beeping conti...

Page 29: ...ectly by the mains Remove excess loads from UPS output first Then shut down the UPS and restart it Fault code is shown as 43 The icon lights on LCD display and alarm beeps continuously UPS is overloaded too long and becomes fault Then UPS shuts down automatically Remove excess loads from UPS output and restart it Fault code is shown as 14 the icon lights on LCD display and alarm beeps continuously...

Page 30: ...ions subject to change without notice Copyright 2022 ABB All rights reserved Specifications subject to change without notice ABB India Helpline Technical telephone support for customers and channel partners Toll free BSNL 91 1800 420 07 07 abb com ups ...

Reviews: