POWERVALUE 11T IN —
6-10 KVA
09: Battery maximum discharge time setting
Interface
Settings
Parameter 3:
000~999:
Set the maximum discharge time from 0 min. to 999 min. UPS will shut
down to protect battery after discharge time arrives. The default value is 990 min.
DIS:
Disable battery discharge protection and backup time will depend on battery
capacity.
10: Reserved
Interface
Settings
Reserved
11: Reserved
Interface
Settings
Reserved
12: Reserved
Interface
Settings
Reserved
13: Battery voltage calibration
Interface
Settings
Parameter 2:
Select “Add” or “Sub” function to calibrate battery voltage to
real figure.
Parameter 3:
The voltage setting range is from 0V to 5.7V. The default value
is 0V.
14: Reserved
Interface
Settings
Reserved
15: Inverter voltage calibration
Interface
Settings
Parameter 2:
you may choose Add or Sub to calibrate inverter voltage
Parameter 3:
The voltage setting range is from 0V to 6.4V. The default
value is 0V.