FIELDBUS COMMUNICATION
STATUS
Approved
SECURITY LEVEL
Public
DOCUMENT ID.
1SFC132374M0201
REV.
B
LANG.
en
PAGE
20/23
© Copyright 2019 ABB. All rights reserved.
Address for data access to de-
vice connected to port
Bit
Data
Description
1
2
3
4
C00h C20h
C40h C60h 0
Reset possible on ac-
tive event
Current fault or protection
can be reset
1
Software fault
Internal fault
2
Shunt fault
Current is flowing when it
should not
3
By-pass open
By-pass does not close
4
Softstarter overload
Too high thyristor- or heat
sink temperature
5
Phase loss
No voltage in one or more
phases on the line side
6
Bad network quality
Bad network quality on
the line side
7
Current loss
Current is not flowing
when it should
8
Fieldbus fault
Fieldbus communication
failure
9
Low supply voltage
Too low control supply
voltage
10
High current
Too high current
11
Motor overload
Too high motor tempera-
ture
12
Locked rotor protec-
tion
Current is higher than set-
table value during top of
ramp
13
Underload protection Current is lower than set-
table value during top of
ramp
14
Reserved
15
Reserved
C01h
C21h
C41h
C61h
0..15
Reserved
C02h
C22h
C42h
C62h
0..15
Reserved
C03h
C23h
C43h
C63h
0
Reserved
1
Reserved
2
Reserved
3
Reserved
4
Parameter is read-
only
This bit is set if a parame-
ter write operation failed
due to the parameter be-
ing read-only.