FIELDBUS COMMUNICATION
STATUS
Approved
SECURITY LEVEL
Public
DOCUMENT ID.
1SFC132374M0201
REV.
B
LANG.
en
PAGE
15/23
© Copyright 2019 ABB. All rights reserved.
4.
Modbus TCP Register Map
The following chapter shows how to generally access data of the FBP-devices connected to
port one to port four of the MTQ22-FBP.
Information
Modbus TCP counts registers beginning with one. But on the bus registers start
counting from zero. The addresses in this manual describe the addresses that are
transmitted on the network. Depending on your client application it might be nec-
essary to increment all addresses by one.
The I/O-data as well as diagnostic and configuration data of the connected PSE devices can
be accessed applying the supported Modbus function codes. The supported functions can be
found in respective sub section.
4.1.
Digital Input Telegram
To read the digital input telegram, use Modbus function code 1
Read Coil Status or 2 Read Discrete Inputs.
Address for data access to device connected
to port
Data
Description
1
2
3
4
1000h
1010h
1020h
1030h
Reserved
1001h
1011h
1021h
1031h
Stop
0 = Motor running
1 = Motor stopped
1002h
1012h
1022h
1032h
Run
0 = Motor stopped
1 = Motor running
1003h
1013h
1023h
1033h
Reserved
1004h
1014h
1024h
1034h
Reserved
1005h
1015h
1025h
1035h
Auto mode1
0 = Local control
1 = Modbus master con-
trol
1006h
1016h
1026h
1036h
Fault
0 = No active fault
1 = One or more active
faults
1007h
1017h
1027h
1037h
Reserved
1008h
1018h
1028h
1038h
Reserved
1009h
1019h
1029h
1039h
DI_FBP_Trip
0 = No trip on DI_FBP
adaptor
1= Trip on DI_FBP adaptor
100Ah
101Ah
102Ah
103Ah
DI_FBP_Local 0 = Remote control
1 = Local control