5.
Fieldbus Operation When Fault
This parameter is accessible only if Fieldbus Control is previously set to On.
In case of fieldbus malfunction, for instance due to power loss or a broken cable, this param-
eter allows for different (operations in case of a fault) reactions to the fault.
Setting Fieldbus fault reaction to trIP will make the softstarter trip on a fieldbus fault. Select-
ing trIP makes reset of the fault necessary, in case of a tripping event.
When LocC is selected, the control of the
softstarter will automatically switch from
fieldbus control to local control. The switch to
local control will make hard-wire control possi-
ble. When the Fieldbus starts working again
the control is automatically switched back to
the Fieldbus. There is a 10 second delay before
it is possible to controlling the motor.
Default value
Setting range
Description
LooC
Looc/trlP
Trip on fieldbus fault or au-
tomatically move to local
control on fieldbus fault
6.
Type of Operation for Reset of Fieldbus Fault
Select what operation shall be asserted if a fieldbus communication fault occurs. Manual or
automatic options are available. HAnd is the default value for reset of Fieldbus Fault:
–
If HAnd is selected - The motor will stop and
manual reset is required.
–
If Auto is selected - The motor will stop and
automatic reset is performed.
This parameter is accessible only if trIP is previ-
ously selected for the parameter fieldbus Oper-
ation When Fault.
Default value
Setting range
Description
HAnd
HAnd/Auto
Hand require manual reset of
fieldbus fault while Auto will
perform the reset automati-
cally.