Value
Description
System option
and interface
Yes/No
This option should be selected, if the database mirroring
functions are used and this system acts as a Host. The
Host is the system that provides process data to another
system.
Database mirror-
ing HOST
For example, if you use mirroring between a communica-
tion server (front-end) and a system server, the commu-
nication server is the host.
Yes/No
This option should be selected, if the database mirroring
functions are used and this system acts as an Image. The
Image is the system that receives process data from an-
other system.
Database mirror-
ing IMAGE
For example, if you use mirroring between a communica-
tion server and a system server, the system server is the
Image.
Yes/No
This option enables the OPC DA server function. The
option should be selected, if the system is to be connected
to an external OPC DA Client e.g. 800xA, HIS 600.
OPC DA Server
0...3
This option is primarily intended for HSB systems, to which
an external OPC DA client is connected e.g. HIS 600.
Application OPC
Server
This Application OPC server is installed in the OPC DA
Client computer and provides an OPC DA server interface
that automatically connects to the Hot application of the
HSB system.
Note: There is NO A&E server interface in this option.
Yes/No
This option enables the OPC A&E server function (Alarms
& Events). The option should be selected, if the system
is to be connected to an external OPC A&E Client e.g.
800xA.
OPC A&E Server
0...4
This is a DA Client that is loosely coupled to the SYS 600
base system and can therefore be installed also in a
separate computer.
OPC DA Client
/External
It is used to connect OPC DA servers to SYS 600. You
need one client for each server that is to be connected.
Note: This DA client is used with the IEC 61850 OPC
server, but you do not have to select this option due to
the IEC 61850 communication.
0...4
The OPC DA client is used to connect foreign devices to
SYS 600 with the OPC DA interface.
OPC DA Client
You need one client for each server that is to be connec-
ted.
The DA client is tightly integrated with the process data-
base and run always on the SYS 600 computer.
33
SYS 600C 2.93
MicroSCADA Pro
Product Guide
1MRS757729
16.11.2012
Issued:
A/16.11.2012
Version: