![ABB J2013001 Quick Start Manual Download Page 4](http://html1.mh-extra.com/html/abb/j2013001/j2013001_quick-start-manual_3045478004.webp)
QUICK START GUIDE
Page 4
© 2021 ABB. All rights reserved.
Return Lug
Landings
-
48V Lug Landings
Rear Battery Lug Landings
(front figure below)
Step 6
-
Connect Batteries
-
skip if not present
Battery connections are labeled
“
-
48
Vdc BATT
”
and
“
POS RTN
”.
Battery connections are either on the rear or front.
Only front battery connections have breakers.
CAUTION:
•
Verify battery voltage and polarity with a voltmeter before proceeding.
•
Front Connections only:
Verify that breaker is OFF or not installed.
1.
Remove Cover
2.
Connect cables with suitable lugs to
-
48Vdc BATT and POS RTN landings.
3.
Torque to 65 in
-
lb (7.3 Nm)
-
7/16”
socket
4.
Replace cover.
Step 7
-
Connect Bullet Circuit Breaker Loads
-
skip if not present
Load connections are labeled
“
-
48
Vdc LOAD
”
and
“
POS RTN
”.
Load Breakers have Black handles.
CAUTION: Verify that breaker is OFF or not installed
1.
Remove Cover
2.
Connect wires with suitable lugs to
-
48Vdc LOAD and POS RTN landings.
3.
Torque per table
4.
Replace Cover
-
Return Lug Landings
-
48V Lug Landings
Cover Screws
2
-
Circuit Blocks
-
Battery or Load