4 - 6
WBPEEUI240766B0
Field Calibration
disabled. All other channels are not affected and continue pro-
cessing input data according to the configuration data.
Before performing a point field calibration, ultra stable,
known, precise values are connected to the input channel.
During point calibration, the ASI module reads the input and
stores its digitized value. Two point calibrations within an
input range must be performed. All these adjustment factors
are calculated and stored in the ASI module’s nonvolatile
memory when the point is enabled.
Precision voltage values are required for low level, thermocou-
ple, and high level input field calibration. For RTD input cali-
bration, precision resistance values are used. FC 217 and the
same procedure is used for all three field calibrations.
Each input channel must be enabled before normal input scan
processing is resumed. The enable command indicates to the
ASI module that the calibration process is completed. At that
time the ASI module stores the field calibration values in non-
volatile memory. The module uses these values during input
scan processing to calculate the correction factors for the cali-
brated channel.
If no field calibration is performed, or if the escape command
was issued to cancel the calibration, the new calibration cor-
rection values are not computed and the previous correction
factors will continue to be used. There is no change to the cali-
bration of the point. The quality of the input point remains bad
after an enable command until a successful input scan is per-
formed for that point. If either the controller or the ASI module
is stopped, or placed into configure mode while a field calibra-
tion sequence is in progress (before an enable is issued), the
field calibration sequence is aborted and must be restarted.
Once the ASI module is calibrated, no further manual calibra-
tion is necessary. Onboard, low-drift references maintain the
accuracy of the calibration.
Procedure
The original ASI module calibration is performed in the factory
in a controlled, stable environment. Ambient temperature
must remain constant at 25 (±1.0) degrees C. The field calibra-
tion location must be free from drafts.
Summary of Contents for IMASI13
Page 1: ...Instruction Harmony Series Analog Input Module IMASI13 ...
Page 11: ...WBPEEUI240766B0 ...
Page 21: ...WBPEEUI240766B0 ...
Page 31: ...WBPEEUI240766B0 ...
Page 41: ...WBPEEUI240766B0 ...
Page 51: ...WBPEEUI240766B0 ...
Page 61: ...WBPEEUI240766B0 ...
Page 81: ...WBPEEUI240766B0 ...
Page 93: ...WBPEEUI240766B0 ...
Page 105: ...WBPEEUI240766B0 ...
Page 111: ...WBPEEUI240766B0 ...
Page 121: ...WBPEEUI240766B0 ...
Page 127: ...WBPEEUI240766B0 ...