ABB i-bus
®
KNX
Parameters
34 9AKK108467A5941 Rev. B | MG/S 11.100.1.1 | EN | Product Manual
Note about navigation in the PDF: Key combination
'Alt + left arrow' jumps to the previous view/page
7.2.1.7
Response Timeout
This parameter defines how many milliseconds the gateway waits between sending a request to a server
and receiving a response.
If the gateway receives a response before this time elapses, it resets the timer and continues polling.
If the gateway does not receive a response, it re-sends the request. The gateway repeats the request
three times before reporting the error via the corresponding Error Status Group Objects.
Option
100 … 1000 … 2000 ms
Note
Some servers have long processing times. This information is usually provided in the server manual.
Take this into account when setting the
Response Timeout
parameter.
Prerequisites for visibility
•
This parameter is in the
General
parameter window.
7.2.1.8
Interframe Timeout
This parameter defines how many milliseconds the gateway waits between receiving and sending a
Modbus telegram. The Modbus load generated by the device can be limited using the
Interframe Timeout
parameter. This limit relates to all Modbus telegrams sent by the device.
Option
0 … 60 … 10000 ms
Prerequisites for visibility
•
This parameter is in the
General
parameter window.