6.2.8. Dip Switches and their function
The position of the dip-switches should only be
read after disconnecting the power supply with
subsequent complete discharge of capacitors.
Setting the dip-switches is only to be performed
with the power supply disconnected and
capacitors completely discharged.
PRODUCT FAMILY: FSK II +
- OPERATING AND MAINTENANCE MANUAL
18
PRODUCT FAMILY: FSK II +
- OPERATING AND MAINTENANCE MANUAL
18
1V
S
R
6
3
0
2
0
6
E
N – e
n – E
D
O
-D
0
0
0
2
8
5
2
– I
n
st
ru
ct
io
n m
an
u
al – 2
0
21
.1
0 D
es
ig
n a
n
d s
p
ec
if
ic
at
io
n a
re s
u
b
je
ct t
o c
h
an
g
e w
it
h
o
ut n
o
ti
ce
—
6. Technical Data
DANGER! IMPORTANT!
6.2.8.1. I1001 Undervoltage threshold
With this switch, the threshold value of the
undervoltage trip is set.
6.2.8.2. I1002 Auxiliary-OFF, HW driven Safe–OFF,
Delay On/Off, Undervoltage Behaviour
Dip Switch I1001
Nominal Voltage
[Un]
Tolerance Range
[35% Unmax and
70% Unmin]
1 2 3
ON
OFF
X
X
X
220…240 VAC/DC
84.0 … 154.0 VAC/DC
ON
X
OFF
X
X
100…127 VAC/DC
44.45 … 70.0 VAC/DC
ON
X
OFF
X
X
60 VDC
21.0 … 42.0 VDC
ON
X
OFF
X
X
48 VDC
6.8 … 33.6 VDC
Table 8 Dip Switch I1001
Dip Switch I1002
Auxiliary-tripping
1 2 3
ON
OFF
X
For BI Y3
ON
X
OFF
HW driven Safe–tripping
For BI Y3
ON
OFF
X
Delay for Opening/Closing
Slow Close Toperation = 10ms delay
Slow Trip Toperation = 10ms delay
For BI Y1
For BI Y2 / Y3
ON
X
OFF
Fast Close Toperation = 3ms delay
Fast Trip Toperation = 3ms delay
For BI Y1
For BI Y2 / Y3
ON
OFF
X
Undervoltage Behaviour
CB Blocked in Open position
ON
X
OFF
CB Closing allowed, but then autotripping by the undervoltage function
(delay set by DIP I1004)
Table 9 Dip Switches I1004-2/3/4