I N S T A L L A T I O N P R O C E D U R E S
FOX615
Installation
69
DUPF1 alarm interface con-
nection
Proceed as follows:
1. Tie the DUPF1 power and alarm cable from below the cable clamp (not
shown in
) along the right bracket of the subrack up to the
FAMO1
or FAMO1-F.
2. Plug the Molex connector to the F5 interface of the FAMO1
or FAMO1-F.
3. Secure the DUPF1 alarm cable in cable clamp (22).
4. Check the lock of the Molex connector for safe fit.
5. Arrange the cable in such a way that it does not block the fixing slots for
the subrack front cover in the brackets.
End of instruction
Please note:
The DUPF1 connector does not use the remaining 2 alarm inputs. If required
these inputs can be used for other alarm signals.
3.7.3.4
Alarm signal output interface
The FAMO1
or FAMO1-F provides the interface F2 for the output of the 2
system alarm signals:
• Service Affecting Alarm (SAA)
• Service Not affecting Alarm (SNA)
Figure 42: FAMO1
and FAMO1-F alarm signals output interface
The alarm signal output interface F2 uses a pin assignment as follows:
Figure 43: Molex connector frame system alarm signal outputs
For the connection of alarm signals Mini-Fit HCS
TM
crimp terminals are
implemented within the Molex connector frame as described in the table
below.
SxA_make
: The contact closes if the alarm becomes active =
AC
F3 : Alarm inputs
1 -4
F4: Alarm inputs
5-8
F5: Alarm inputs
9-12
F2: Alarm output
1-2
50
moving fans
refer to handbook
F2
fan 48 VDC 19" 1U
37970003
R2A
2111743473
2011 W44
1
2
3
4
5
6
Table 8:
Alarm output interface pin connection
Alarm Type
Pin
Pin
Pin
Non Urgent
SNA_make
6
SNA_break
5
SNA_com
4
Urgent
SAA_break
3
SAA_make
2
SAA_com
1
Summary of Contents for FOX615
Page 1: ...ABB Power Systems FOX615 Installation User Manual ...
Page 6: ...4 FOX615 Installation ...
Page 10: ...8 FOX615 Installation ...
Page 96: ...A N N E X 94 FOX615 Installation ...
Page 97: ......