![ABB FEP315 Original Instruction Download Page 19](http://html.mh-extra.com/html/abb/fep315/fep315_original-instruction_4407019.webp)
Mounting
SM/FEX300/FEX500/FM/CSA-EN
FEX300, FEX500
EN - 17
4.2
Rotating the transmitter housing
Dual compartment housing
Single compartment housing
Fig. 9
1.
Loosen the Allen screws (3) on the front and back sides, but do not remove entirely.
2.
Loosen screws (2) and rotate the transmitter housing (1) by 90° to the left or right.
3.
Retighten screws (2) and Allen screws (3).
DANGER - Risk of explosion!
When the screws for the transmitter housing are loosened, the explosion protection is
suspended.
Tighten all screws (2, 3) for the transmitter housing prior to commissioning.
4.3 Cable
entries
Dual compartment housing
Single compartment housing
Fig. 10
The devices are delivered with 1/2" NPT or PF 1/2" threads with protective shipping plugs (1).
Unused cable entries must be closed prior to commissioning using either approved threaded
pipe connections or cable glands according to national regulations (NEC, CEC).
Make sure that the threaded pipe connections, cable glands and possibly plugs are installed
properly and sealed.
If the device is to be operated in areas with combustible dusts, a threaded pipe connection or
cable gland with suitable approval must be used.
G00
7
6
1-
0
1
1
3
2
3
3
G00
759-
0
1
1
1
1
1
Summary of Contents for FEP315
Page 2: ......
Page 44: ...Appendix 42 EN FEX300 FEX500 SM FEX300 FEX500 FM CSA EN ...
Page 46: ...Appendix 44 EN FEX300 FEX500 SM FEX300 FEX500 FM CSA EN ...
Page 47: ......