1SDH000510R0001
21/28
Page N.
L2388
EP010
ABB SACE
4
Product Standard reference
IEC | UL1066
0 | 1
2
IEC
Yes
5
Tri/Tetra poles
3 | 4 poles
0 | 1
2
3 poles
Yes
6
In (nominal current)
250 | 400 | 630 | 800 | 1000 |
A
2
250
Yes
1250 | 1600 | 2000 | 2500 |
3200 | 4000 | 5000 | 6300
7
CB type
See table page 26
2
Yes
8
CB Serial Number 1
1 byte for char.
8
Yes
(ASCII)
9
CB Serial Number 2
1 byte for char.
8
Yes
(ASCII)
10 Datalogger max file
{0 ... 3}
2
0
Yes
11 Datalogger max address
2
0
Yes
12 Datalogger Trigger
None (free running)|Any Alarm|
0 | 1 | 2 | 3 | 4
2 None
Yes
L Timing | Any Trip | Custom
13 Day od Dlogger trigger
Number of days from 31/12/1999
2
Yes
14 Hour & minute of Dlogger trigger
h.min
2 MBS = Hour
Yes
LBS = minute
15 Second of Dlog trigger
{0 ... 59}
s
2
Yes
16 Millisecond of Dlog trigger
{0 ... 99}
ms
2
Yes
17 CB name 1
1 byte for char.
6
Yes
(ASCII)
18 CB name 2
1 byte for char.
6
Yes
(ASCII)
19 Product execution
LI | LSI | LSIG | LSIRc
0 | 1 | 2 | 3
2
LI
Yes
20 Relay serial Number 1
1 byte for char.
8
Yes
(ASCII)
21 Relay serial Number 2
1 byte for char.
8
Yes
(ASCII)
22 Unit configuration
2
Yes
0 : Rc range 0.3 ... 3 [A]
Rc range 0.3 ... 3 [A] (Idn = 1A) |
0 | 1
Rc range 3 ... 30 [A] (Idn = 10A)
1: Local Bus Unit
Absent | Present
0 | 1
2: VT
Absent | Present
0 | 1
3 : Neutral Protection
OFF | ON
0 | 1
4: PowerDir
Top | Bottom
0 | 1
5: Neutral Voltage
Absent | Present
0 | 1
6: Operating mode
Local | Remote
0 | 1
7-15: not used
23 Language
ENG | ITA | FRA | GER | SPA
0 | 1 | 2 | 3 | 4
2 English
Yes
24 Neutral selection
50% | 100% | 150% | 200%
0 | 1 | 2 | 3
2
100%
Yes
25 Ext. ground toroid
100 | 250 | 400 | 800
A
0 | 1 | 2 | 3
2
100
Yes
26 Nominal voltage Un
See table page 26
2
100
Yes
27 VT secondary voltage
100 | 110 | 115 | 120 | 200 | 230
V
0 | 1 | 2 | 3 | 4 | 5
2
100
Yes
28 Net frequency
50 | 60
Hz
0 | 1
2
50
Yes
29 Plant Configuration
3P | 3P+N
0 | 1
3
3P
Yes
30 Slave Address
{1 ... 247}
2
247
Yes
31 Addressing Type
Standard | ABB
0 | 1
2 Standard
Yes
32 Baud rate
9600 | 19200
0 | 1
2
19200
Yes
33 Protocol Type
E.8.1 | O.8.1 | N.8.2 | N.8.1
0 | 1 | 2 | 3
2
E.8.1
Yes
34 Ext Toroid Type
None|Source Ground Return|Rc
0 | 1 | 2
none
Yes
35 Configuration
2
0: Parameter Set
Set A | Set B
0 | 1
Yes
1: Dual Setting
OFF | ON
0 | 1
Yes
2: Harmonic Distortion Warning
OFF | ON
0 | 1
3: Phase Rotation Warning
OFF | ON
0 | 1
Yes
4. Phase Rotation Cycle
123 | 321
0 | 1
Yes
5: Cos
j
Module warning
OFF | ON
0 | 1
Yes
6: Dualset CB Close
Disable | Set B on CB Close
0 | 1
Yes
7: Dualset Vaux
Disable | Set B on Vaox OFF
0 | 1
Yes
8-15: not used
36 Measurements store time
{5 ... 120}, step 5
min
2
5
37 Loc Bus Relais Unit Contact config
0: Relè K51/1
Not Latched | Latched
0 | 1
1: Relè K51/2
Not Latched | Latched
0 | 1
2: Relè K51/3
Not Latched | Latched
0 | 1
3: Relè K51/4
Not Latched | Latched
0 | 1
4: Relè K51/6
Not Latched | Latched
0 | 1
5: Relè K51/7
Not Latched | Latched
0 | 1
6: Relè K51/8
Not Latched | Latched
0 | 1
7: Contact K51/1
NO | NC
0 | 1
8: Contact K51/2
NO | NC
0 | 1
9: Contact K51/3
NO | NC
0 | 1
10: Contact K51/4
NO | NC
0 | 1
11: Contact K51/6
NO | NC
0 | 1
12: Contact K51/7
NO | NC
0 | 1
13: Contact K51/8
NO | NC
0 | 1
14-15: not used
38 Local Bus Relais 1 Function
None | L prealarm | L timing |
{0 ... 65535}
2
None
S Timing | L trip | S trip | I trip |
G trip| Any trip| Any Alarm| LC1|
LC2 | Custom
39 Loc Bus Relais 1 Delay
{0.00 ... 100.00}, step 0.01
s
100
2
0
40 Loc Bus Relais 2 Function
None | L prealarm | L timing |
{0 ... 65535}
2
None
S Timing | L trip | S trip | I trip |
G trip| Any trip| Any Alarm| LC1|
LC2 | Custom
41 Loc Bus Relais 2 Delay
{0.00 ... 100.00}, step 0.01
s
100
2
0
42 Loc Bus Relais 3 Function
None | L prealarm | L timing |
{0 ... 65535}
2
None
S Timing | L trip | S trip | I trip |
G trip| Any trip| Any Alarm| LC1|
LC2 | Custom
# Name/Description
Range
Units Multipler Coding
Lenght
Range
Notes
Read only
PR123 only
[bytes]
default