1SDH000510R0001
23/28
Page N.
L2388
EP010
ABB SACE
5-15: not used
83 Prot S curve type
T=k | I
2
t = k
0 | 1
2
T=k
84 Prot S threshold T=k/I
2
{0.6 ... 10.0}, step 0.1
In
100
2
0.6
85 Prot S time T=k/I
2
{0.05 … 0.8}, step 0.01
s
100
2
0.05
86 Prot S threshold T=k
{0.6 ... 10.0}, step 0.1
In
100
2
0.6
87 Prot S time T=k
{0.05 … 0.8}, step 0.01
s
100
2
0.05
88 Prot S start up threshold
{0.6 ... 10.0}, step 0.1
In
100
2
0.6
89 Prot S start up time
{0.10 ... 1.50}, step 0.01
s
100
2
0.1
90 Prot S zone selectivity time
{0.04 ... 0.20}, step 0.01
s
100
2
0.04
91 Prot S2 configuration
2
Yes
0: Prot enable/disable
Enable | Disable
0 | 1
1: not used
2: Start Up Th
OFF | ON
0 | 1
3: Zone sel
OFF | ON
0 | 1
4-15: not used
92 Prot S2 threshold T=k
{0.6 ... 10.0}, step 0.1
In
100
2
0.6
Yes
93 Prot S2 time T=k
{0.05 … 0.8}, step 0.01
s
100
2
0.05
Yes
94 Prot S2 start up threshold
{0.6 ... 10.0}, step 0.1
In
100
2
0.6
Yes
95 Prot S2 start up time
{0.10 ... 1.50}, step 0.01
s
100
2
0.1
Yes
96 Prot S2 zone selectivity time
{0.04 ... 0.20}, step 0.01
s
100
2
0.04
Yes
97 Prot D configuration
2
Yes
0: Prot enable/disable
Enable | Disable
0 | 1
1: not used
2: Start Up Th
OFF | ON
0 | 1
3: Zone sel
OFF | ON
0 | 1
4-15: not used
98 Prot D threshold
{0.6 ... 10.0}, step 0.1
In
100
2
0.6
Yes
99 Prot D time Forward
{0.2 … 0.8}, step 0.01
s
100
2
0.2
Yes
100 Prot D time Backward
{0.2 … 0.8}, step 0.01
s
100
2
0.2
Yes
101 Prot D start up threshold
{0.6 ... 10.0}, step 0.1
In
100
2
0.6
Yes
102 Prot D start up time
{0.10 ... 1.50}, step 0.01
s
100
2
0.1
Yes
103 Prot D zone selectivity time
{0.13 ... 0.50}, step 0.01
s
100
2
0.13
Yes
104 Prot I configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: not used
2: Start Up Th
OFF | ON
0 | 1
3-15: not used
105 Prot I threshold
{1.5 ... 15}, step 0.1
In
100
2
1.5
106 Prot I start up threshold
{1.5 ... 15}, step 0.1
In
100
2
1.5
107 Prot I start up time
{0.10 ... 1.50}, step 0.01
s
100
2
0.1
108 Prot G configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2: Start Up Th
OFF | ON
0 | 1
3: Zone sel
OFF | ON
0 | 1
4-15: not used
109 Prot G curve type
T=k | I
2
t = k
0 | 1
2
T=k
110 Prot G threshold T=k/I
2
{0.20 ... 1.00}, step 0.02
In
100
2
0.2
111 Prot G time T=k/I
2
{0.01 … 1.00}, step 0.05
s
100
2
0.01
112 Prot G threshold T=k
{0.20 ... 1.00}, step 0.02
In
100
2
0.2
113 Prot G time T=k
{0.01 … 1.00}, step 0.05
s
100
2
0.01
114 Prot G start up threshold
{0.20 ... 1.00}, step 0.02
In
100
2
0.2
115 Prot G start up time
{0.01 … 1.00}, step 0.05
s
100
2
0.01
116 Prot G zone selectivity time
{0.04 ... 0.20}, step 0.01
s
100
2
0.04
117 Prot Ext G configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2: Start Up Th
OFF | ON
0 | 1
3: Zone sel
OFF | ON
0 | 1
4-15: not used
118 Prot Ext G curve type
T=k | I
2
t = k
0 | 1
2
T=k
119 Prot Ext G threshold T=k/I
2
{0.20 ... 1.00}, step 0.02
In
100
2
0.2
120 Prot Ext G time T=k/I
2
{0.01 … 1.00}, step 0.05
s
100
2
0.01
121 Prot Ext G threshold T=k
{0.20 ... 1.00}, step 0.02
In
100
2
0.2
122 Prot Ext G time T=k
{0.01 … 1.00}, step 0.05
s
100
2
0.01
123 Prot Ext G start up threshold
{0.20 ... 1.00}, step 0.02
In
100
2
0.2
124 Prot Ext G start up time
{0.01 … 1.00}, step 0.05
s
100
2
0.01
125 Prot Ext G zone selectivity time
{0.04 ... 0.20}, step 0.01
s
100
2
0.04
126 Prot U configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
127 Prot U threshold
{5 ... 90}, step 5
%
2
5
128 Prot U time
{0.5 ... 60}, step 0.5
s
100
2
0.5
129 Prot UV configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
130 Prot UV threshold
{0.50 ... 0.95}, step 0.01
Un
100
2
0.50
131 Prot UV time
{0.1 ... 5.0}, step 0.1
s
100
2
0.1
132 Prot OV configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
133 Prot OV threshold
{1.05 ... 1.20}, step 0.01
Un
100
2
1.05
134 Prot OV time
{0.1 ... 5.0}, step 0.1
s
100
2
0.1
135 Prot RV configuration
2
0: Prot enable/disable
Enable | Disable
0 | 1
1: Trip enable/disable
Enable | Disable
0 | 1
2-15: not used
136 Prot RV threshold
{0.10 ... 0.40}, step 0.05
Un
100
2
0.1
# Name/Description
Range
Units Multipler Coding
Lenght
Range
Notes
Read only
PR123 only
[bytes]